Shrewdness and precautions
o
NO
For vertical installations with
descending flow direction
contact the manufacturer
Avoid the installation of the
sensor in a long pipe,
without any support of the
LONG PIPE
same
Avoid operating when the
pipe is partially empty
Avoid the installation next to
bows in pipes and respect
min. inlet and outlet sections
Avoid the approach of the
flange and counter flange
using the closing force of
the nuts
OPERATING TEMPERATURES
EBONITE LINING
Ambient
Liquid Temp.
Temp.
Min.
Max
Min.
° C
0
80
-5
° F
30
176
23
SENSOR FOR ELECTROMAGNETIC FLOW METER – MANUAL
LONG PIPE
GASKET THICKNESS + 4mm
PP LINING
Ambient
Liquid Temp.
Temp.
Max
Min.
Max
Min.
60
0
60
0
140
32
140
32
5
YES
For vertical installations is
preferable an ascending flow
ANTI VIBRATION JOINTS
For installations on long
pipes, please use the
anti vibration joints
During operation, the pipe
must be either completely full
of liquid, or completely empty
3 X DN
Install the sensor at a min.
distance to bows in pipes and
2 X DN
hydraulic accessories
Before tightening the nuts,
place both the flanges of pipe
and device as near together
as possible.
PTFE LINING
Ambient
Liquid Temp.
Temp.
Max
Min.
Max
Min.
60
-20
130
-10
140
-4
266
14
ESENS_FULLBORE_05.doc
Max
60
140