Table des Matières

Publicité

Les langues disponibles

Les langues disponibles

WARNING
WARNING
with a three-prong (grounding) plug for your
protection against shock hazard and should be
plugged directly into a properly grounded three-
prong receptacle.
WARNING
ALWAYS install the heater so that it is not directly
exposed to water spray, rain, dripping water, or wind.
Use heater in accordance with all local codes. In
the absence of local codes, refer to The National
Fuel Code, ANSI A223.1/NFPA 54.
This heater is shipped from the factory for use with
propane (LP) gas only. Do not convert to any other
gas. Installation must conform to local codes, or
in their absence, with the standard for the Storage
and Handling of Liquefied Petroleum Gases
ANSI/NFPA 58 and the Natural Gas and Propane
Installation Code CSA B149.1.
WARNING
Figure 1
1. Remove all packing items applied to heater for
shipment. Keep plastic cover caps attached to inlet
connector and hose / regulator assembly for storage.
2. Remove all items from carton
3. Check all items for shipping damage. If the heater
is damaged, promptly inform dealer where you
purchased the heater.
© 2019 Pinnacle Climate Technologies, Inc.
NEVER LEAVE HEATER UNATTENDED WHILE BURNING OR
®
SAFETY INFORMATION (CONT.)
RISK OF ELECTRIC
SHOCK!
Electrical Ground-
ing Instructions: This
appliance is equipped
For use with propane
(LP) gas only.
RISK OF FIRE! DO NOT POSITION HEATER IN A DOWNWARD ANGLE.
ALWAYS LOCATE HEATER ON A STABLE AND LEVEL SURFACE (SEE
FIGURE 1)!

UNPACKING

WHILE CONNECTED TO A POWER SOURCE
Gas supply connections should be checked by
using a 50/50 soap and water solution. Never use a
flame to check for gas leaks.
Locate LP cylinder at least 6 ft. (183 cm) (10
ft./305 cm in Canada) from the heater, and do not
direct heater discharge towards the LP cylinder
unless it is at least 20 feet (610 cm) from the
heater.
Use only the regulator and hose assembly provided
with this heater. Inspect the regulator/hose
assembly prior to each use of the heater. If there
is excessive abrasion or wear, or if the hose is cut,
replace it with the proper assembly shown in the
parts list, prior to using the heater.
Manifold, Minimum, and Maximum Inlet Pressure
40-GFA
11" (279
Man.
mm) W.C.
Min.
Max.
WARNING
material and contact with hot surfaces both dur-
ing use and while in storage.
X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X
X
CAUTION
sembly supplied with the heater must be used
without alteration.
5
Propane Forced Air Heater User's Manual
60V-GFA
125V-GFA
7.8" (198
11" (279
mm) W.C.
mm) W.C.
5 PSI (34.5 kPa)
Bottle Pressure
The hose assembly
shall be pro tected
from traffic, building
The Propane (LP)
gas pressure regula-
tor and hose as-
150V-GFA
8" (203
mm) W.C.

Publicité

Table des Matières
loading

Ce manuel est également adapté pour:

Pt-60v-gfa-aPt-125v-gfa-aPt-150v-gfa-a

Table des Matières