TROUBLESHOOTING
Fault Recall
When the control is in standby mode (no call for heat or
cool), press the "RECALL" button for approximately two – five
seconds.
NOTE: While displaying the stored fault codes, the control
will ignore any new call for heat, cool or fan. Consecutively
repeated faults are displayed a maximum of three times.
Fault Code Reset
When the control is in standby mode (no call for heat or cool),
press the "RECALL" button for five to ten seconds or until the
diagnostic LED begins to rapid flash.
NOTE: If the switch is held pressed for over ten seconds the
rapid flash will stop and the LED will be on to indicate return
to normal status.
Field Test / Short Cycle Delay Bypass
When the control is in standby mode (no call for heat or cool),
FAULT AND STATUS CODES
Fault and Status Codes
The LED will indicate fault or status codes as shown in the table below:
LED 1 LED 2
none
none
No Power
O
n
Standby
0
1
Low Pressure Cut Out Trip / Low Side Fault
0
2
High Pressure Cut Out Trip / High Side Fault
0
3
Short Cycling
0
4
Locked Rotor
0
5
Open Circuit
0
6
Open Start Circuit
0
7
Open Run Circuit
0
8
No Line Voltage
0
9
Low Pilot Voltage
8
8
Power Up
A
2
Outdoor Air Temp Sensor Fault
Outdoor Coil Temp Sensor Fault
A
3
(Heat Pump Only)
b
0
No Indoor Airflow
b
9
Low Indoor Airflow
C
3
Cool Mode Short Cycle Timer
C
1
Low Cool
C
2
High Cool
d
F
Defrost (Heat Pump Only)
NOTE: LED 3 (DS3) is not used at this time
Emerson and White-Rodgers are
trademarks of Emerson Electric Co.
©2017 Emerson Electric Co. All
rights reserved.
Error / Condition
TECHNICAL SUPPORT: 1-888-725-9797
white-rodgers.com
emerson.com
press the "TEST" button for greater than 1 second for a 5 sec-
ond power check of the compressor and outdoor fan. ACTIVE
delays such as short cycle timer are bypassed, and pressure
switch lockouts are also cleared.
Forced Defrost
Press the "TEST" and "RECALL" buttons simultaneously for
greater than 1 and less than 10 seconds with a call for heat.
Ambient temperature must be below the defrost enable tem-
perature. Cancel by pressing buttons again.
Pumpdown (Communicating System Only)
Press the "TEST" and "LEARN" buttons simultaneously for
greater than 5 and less than 10 seconds with no call present.
Compressor and fan will operate in high stage cooling for up
to 5 minutes and indoor blower will run on high. Cancel by
pressing buttons for 5 to 10 seconds again.
LED 1 LED 2
d
t
Max Defrost Time (Heat Pump Only)
d
E
Forced Defrost (Heat Pump Only)
d
0
Data Not on Network
d
1
Invalid Data on Network
d
3
Configuration Mismatch
d
4
Invalid Memory Card Data
E
E
Board Misoperation
E
5
Open Fuse
F
t
Field Test Mode
H
8
High Line Voltage
L
1
Low Pressure Cut Out Lockout (3 Trips)
L
2
High Pressure Cut Out Lockout (3 Trips)
L
6
Open Start Circuit Lockout
L
7
Open Run Circuit Lockout
L
8
Low Line Voltage
Heat Mode Short Cycle Timer
P
3
(Heat Pump Only)
P
1
Low Heat (Heat Pump Only)
P
2
High Heat (Heat Pump Only)
P
0
Compressor Protector Open
P
d
Pump Down
Error / Condition