Dipswitch Configuration; Torque Requirements - White-Rodgers 49S25-707 Directives D'installation

Table des Matières

Publicité

Les langues disponibles

Les langues disponibles

PSC Outdoor Fan Motor
SW1
30*
60
NOTE:
Cycle power after changes are made.
For best results set dip switches to prior boards configuration or refer to original OEM install manual for further details.
AC / HP Selection
The 49S25-707 control board is designed to be used in either
AC or heat pump applications. Be sure to determine board
application before installation.
For AC application in either 4-wire communicating and
legacy, board may be installed as is using the correct
wiring configuration. DO NOT CUT JUMPER WIRES.
Cutting wires will result in board error which is irreversible.
For heat pump application in either 4-wire communicating
and legacy, both jumper wires depicted in wiring
diagram from page 2 must be cut before installation.
Failure to cut jumper wires will result in error.
Minimum Run Time
Maximum Defrost Cycle
Defrost Termination Time
Compressor / RV Shift Delay (For Noise, Selectable)
Outdoor Fan On / Off Delay
Compressor Staging Delay (1
Field "TEST" Pushbutton (Compressor and Fan Relays Turned On)
Defrost Time (minutes)
90
120
Event
st
Stage to 2
nd
Stage)

DIPSWITCH CONFIGURATION

Termination
SW5
ON*
OFF
ON
OFF
OFF
OFF
ON
OFF
*default

Torque Requirements

Tighten lugs / screws L1 / L2 and compressor R and C using
torque specifications below. Overtightening may result in
wiring failure.
Wire Gauge
# 4 – 6
# 8
# 10 – 14
30 Seconds
10 Minutes
30 Min. Default; 30, 60, 90, 120 Min.
Dipswitch & Comm. Selectable
30 Second Default; 0, 5, 15, 30 Sec. Comm. Selectable
1 Second
5 Seconds
5 Seconds
WIRING DIAGRAM
ON
OFF
ON
OFF
INSTALLATION
Torque (in / lbs)
45
40
35
OPERATION
Timing
3