Installation location and project planning
2.2
Arrangement of smoke alarms in hallways
In rooms and hallways with a width
of < 1 m, the smoke alarm must be
installed at the ceiling in the centre
between the walls.
In hallways and corridors with
a maximum width of 3 m, the
max 7.5 m
max. 3 m
max 7.5 m
Observe national regulations and guidelines.
14
clearance between two smoke
alarms must not exceed 15 m. The
clearance to the end of the hallway
must not exceed 7.5 m.
max. 15 m
max. 3 m
max 7.5 m
max. 15 m
EN
max. 3 m