Terminal
Signal type
Digital
X1/I15
inputs
X1/I16
X1/O5
Digital
outputs
...
X1/O8
^
X2/A
Analog
X2/AI4
inputs
X2/AI5
X2/+O24
^
X2/
24
X4/I9
Digital
inputs
...
X4/I14
(
Stop!
Ensure a sufficient dimensioning of the DC voltage supply, if the loads are
ƒ
connected to the digital outputs.
The extension board must exclusively be supplied separately.The internal
ƒ
supply via the Drive PLC is not permissible.
EDK10203EZ3 DE/EN/FR 4.1
Electrical installation
Assignment of the terminals
Function
Reference potential for
analog signals
DC voltage supply
GND, reference potential
for digital outputs
Technical data
LOW (0 V ... +4 V)
HIGH (+13 V ... +30 V)
Input current: max. 8
mA at 24 V
LOW (0 V ... +4 V)
HIGH (+13 V ... +30 V)
Load capacity: max.
1 A
Input voltage:
−10 V ... +10 V
Resolution:
10 bit + sign
18 VDC ... 30 VDC
LOW (0 V ... +4 V)
HIGH (+13 V ... +30 V)
Input current: max. 8
mA at 24 V
16
Remarks
l
Use shielded
cables
l
Connect the
screen at both
ends
Connected via
emergency off at the
Drive PLC