Anden dehumidifiers can be wired in a daisy chain application, allowing one Model S77 or alternate dry contact dehumidistat to control any number
of dehumidifiers wired together� Reference the dehumidifier Installation and Operation Manual for detailed set-up and operation�
MODEL S77 AS DRIVING CONTROL
When a Model S77 is used to control the first dehumidifier, Unit #1 must be set to ENABLE REMOTE in the set-up menu� All downstream units must
be set up to ENABLE EXTERNAL in each set-up menu� See page 12 for set up details, and wire as shown in FIGURE 12�
SEQUENCE OF OPERATION
Each unit in the daisy chain responds to the first unit being controlled by the S77� When the humidity level rises above the humidity setting, all units
will dehumidify until the humidity measured by the S77 falls below the setting�
IMPORTANT: If the S77 or first dehumidifier experiences a fault or loses power, all downstream dehumidifiers will also stop function� If any
dehumidifier in the daisy chain other than Unit #1 experiences a fault, that unit will stop operation as determined by the fault but all other units will
continue operating� If any dehumidifier loses power, all downstream units will stop function�