7 . S p e c i f i c a t i o n s
GENERAL CHARACTERISTICS
CAPACITY*
Dimension,
DXWXH (mm)
Net Weight (kg)
INPUT
Acceptable Voltage
Range
Frequency Range
OUTPUT
Voltage Regulation
(normal Mode)
Voltage Regulation
(Batt. Mode)
Frequency Range
(Batt. Mode)
Current Crest Ratio
Harmonic Distortion
Over load capacity
Waveform
(Batt. Mode)
EFFICIENCY
Normal Mode
AVR Mode
Battery Mode
BATTERY
Battery Type &
Number
Charging Voltage
Recharge Time
PROTECTION
Full Protection
INDICATORS & ALARM
Indicator
Alarms
ENVIRONMENT
Operating Humidity
Elevation
Noise Level
MANAGEMENT/COMMUNICATION
Smart RS-232/USB
Optional SNMP
NORMS
Standards
EMC
LVD
SALES INFORMATION
Warranty
PN IEC (HV)
PN NEMA (HV)
HV : 230V models: 200/208/220/230/240V / LV : 120V models : 100/110/115/120/125V
* Derate capacity to 80% of capacity when the output voltage is adjusted to 208VAC.
Product specifications are subject to change without further notice.
INFOSEC UPS SYSTEM - 15, rue du Moulin - 44880 Sautron - FRANCE - www.infosec-ups.com
Hot Line – Tel + 33 (0)2 40 76 15 82 - Fax + 33 (0)240 94 29 51 - hotline@infosec.fr – 12 18 AA 59 205 19
75-117/81-134/86-139/89-145/102-152 VAC for models 120VAC
150-234/156-243/162-268/170-280/177-290 VAC for models 230VAC
100*(-13%/+10%)/110(-15%/+10%)/115(-14%/+10%)/120(-14%/+10%)/125(-11%/+11%) VAC
200*(-13%/+10%)/208*(-13%/+10%)/220(-15%/+10%)/230(-15%/+10%)/240(-15%/+10%) VAC
100/110/115/120/125 VAC ±1.5%(before low battery alarm) for models 120VAC
200/208/220/230/240 VAC ±1.5% (before low battery alarm) for models 230VAC
2% max @ 100% linear load, 5% max @ 100% non-linear load (before low battery alarm)
103% to 120% Alarm warning with shutdown after 5 minutes (1minutes @ battery mode)
120% to 150% Alarm warning with shutdown after 10 seconds
150% and greater Shutdown UPS Immediately
Overload, short, discharge, and overcharge protection
Battery Mode, Low Battery, Overload, Battery Replacement, Fault
Ambient temperature will require derating of 5 °C for each additional 500 m in altitude.
Supports Windows® 2000/2003/XP/Vista/2008, 7/8/10, Linux, Unix, and MAC
Power management from SNMP (VMWare
E3 Performance 5000 RT
3000 VA / 2700 W
645 x 438 x 88 (2U)
39.8
60/50 Hz (auto sensing)
for models 120VAC
for models 208VAC
50 Hz or 60 Hz ± 1 Hz
3:1
Pure Sine Wave
97%
95%
92%
12 V/10 Ahx6
82.1 VDC ± 1%
4 hours recover to 90% capacity
LCD screen
0-90 % RH @ 0- 40°C (non-condensing)
Up to 3,000m @ 0-40°C without derating.
Less than 45dB at 1 meter
©
compatible) manager and web browser
CE RoHS
EN62040-2: 2006+AC: 2006
EN62040-1:2008+A1:2013
2 years