COMBI WALL MOUNTED GAS BOILER INSTALLATION, OPERATION & MAINTENANCE MANUAL CHAUDIÈRE À GAZ MURALE COMBI MANUEL D’INSTALLATION, D’UTILISATION ET D’ENTRETIEN Manufactured for: ECR International, Inc. 2201 Dwyer Avenue, Utica NY 13501 web site: www.ecrinternational.com P/N# 240010632, Rev. B [07/17/2014] Fabriquée pour : ECR International, Inc.
DIMENSIONS Figure 1 - Overall Dimensions Top View Side View Front View Rear View 1 = 1“ MPT Supply Water to Heating System (Out) 2 = 3/4” MPT Tap Water Outlet 3 = 3/4” FPT Gas Inlet 4 = 3/4” MPT Tap Water Inlet 5 = 1”...
TABLE OF CONTENTS 1 - Introduction ........................4 2 - Important Safety Information ................... 5 3 - General view and main components .................. 6 4 - Locating Boiler ....................... 9 5 - Hydronic Piping ......................11 6 - Combustion Air And Vent Piping - Category I (Chimney Vent) ..........15 6 - Combustion Air And Vent Piping of direct vent and Category III ..........
• Integral Dual Limit. Information and specifi cations outlined in this manual in effect at the time of printing of this manual. ECR International, Inc. reserves the right to discontinue, change specifi cations or system design at any time without...
2 - IMPORTANT SAFETY INFORMATION 2.1 General 2.3 Installation shall conform to requirements of Boiler installation shall be completed by quali ed agency. authority having jurisdiction or in absence of such See glossary for additional information. requirements: • United States •...
3 - GENERAL VIEW AND MAIN COMPONENTS Figure 2 Component Listing...
Page 7
3 - GENERAL VIEW AND MAIN COMPONENTS Item Description Number Sealed Chamber Gas Inlet Domestic Hot Water (DHW) Outlet Domestic Cold Water (DHW) Inlet Supply System System Return Modulating Fan Combustion Chamber Burner Assembly Burner Combustion Chamber Insulation Copper Heat Exchanger Exhaust Manifold Exhaust Outlet Manifold Heating circulating pump...
Page 8
3 - GENERAL VIEW AND MAIN COMPONENTS WARNING Fire, explosion, asphyxiation and electrical shock hazard. Disconnect electrical power supply and turn off gas at shutoff valve before attemting to remove boiler jacket. Failure to follow these instructions could result in death or serious injury.
4 - LOCATING BOILER 4.1 Boiler Location Considerations Figure 5 - Boiler Clearances • Ambient room temperature always above 32°F (0°C) to prevent freezing. • Approved for installation in closets. • Protect gas ignition system components from water (dripping, spraying, rain, etc.) during operation and service (circulator replacement, control replacement, etc.).
4 - LOCATING BOILER Pre-pipe supply and return water connections Figure 6 - Wall Mounting Bracket with factory fi ttings before wall mounting. 4.3 Wall Mounting 2 ” 2 ” Mount boiler on wall using wall mounting bracket included (2.4cm) (2.4cm) with unit.
5 - HYDRONIC PIPING 5.1 General Conditioning chemicals must ensure complete deoxygenation of water and contain speci c protective agents for yellow • Install piping in accordance with authority having jurisdiction. metals (copper and its alloys), anti-fouling agents for NOTICE limescale at least up to 150 ppm CaCO3, pH neutral stabilizers and, in low temperature systems, speci c biocides Use two (2) wrenches when tightening and tting...
Page 12
5 - HYDRONIC PIPING Figure 7 - Safety Relief Valve & Air Vent WARNING (Viewed from front of boiler) Burn and Scald Hazard. Safety relief vlave could discharge steam or hot water during operation. Install discharge piping per these instructions. Failure to do so could result in death or serious injury.
Page 13
5 - HYDRONIC PIPING Figure 8 - Safety Relief Valve Discharge Piping Safety Relief Valve Gas Shutoff Valve in Open position Check Local Codes for Maximum Distance to Floor...
5 - HYDRONIC PIPING Figure 9 - Hydronic Piping - Plumbing circuit 8 Domestic Hot Water Outlet 9 Domestic Cold Water Inlet 10 Heating System Supply 11 Heating System Return 27 Copper Exchanger For Heating And Hot Water 32 Heating Circulating Pump 36 Automatic Air Vent 42 DHW Temperature Sensor 95 Diverter Valve...
6 - COMBUSTION AIR AND VENT PIPING - CATEGORY I (CHIMNEY VENT) Vent connector from boiler to chimney should run as WARNING directly as possible with as few elbows as possible. Boiler and venting installations shall be performed Common venting shall not be allowed. Boiler and by a quali ed expert and in accordance with the other certi ed appliances.
Page 16
6 - COMBUSTION AIR AND VENT PIPING- CATEGORY I (CHIMNEY VENT) 6.2 Minimum Vent Pipe Clearance After it has been determined that each appliance remaining connected to the common venting system • Use Type B vent pipe through crawl space. Where vent properly vents when tested as outlined above, return pipe passes through combustible wall or partition, use doors, windows, exhaust fans, replace dampers and...
4 feet (1.22m) horizontal A. When venting through combustible walls, distance is maintained, from electric meters, gas combustible clearances must be considered. ECR meters, regulators and relief equipment. vent termination, 5612601, is a certi ed direct vent...
Page 18
6 - COMBUSTION AIR AND VENT PIPING OF DIRECT VENT AND CATEGORY III If the horizontal vent must go through a crawl space or WARNING other unheated space, the cool temperatures will likely Vent extending through exterior wall shall not cause the ue gases to continuously condense inside terminate adjacent to wall or below building the vent pipe.
6 - COMBUSTION AIR AND VENTILATION Provide combustion air and ventilation air in accordance • All Outdoor Air. Provide permanent opening(s) with the section “Air for Combustion and Ventilation,” of the communicating directly or by ducts with outdoors. National Fuel Gas Code, ANSI Z223.1/NFPA 54, or Sections Two Permanent Opening Method.
6 - COMBUSTION AIR AND VENT PIPING Figure 11 - Horizontal Venting Clearances NOTICE Maintain 12” (30cm) US, 18” (46cm) Canada Figure 12 - Two Pipe Venting clearance above highest anticipated snow level or grade. = Combustion Air / = Venting)
Page 21
6 - COMBUSTION AIR AND VENT PIPING NOTICE Figure 13 - Chimney Venting with Room Air Single Wall Refer to section 6.1, numbers 3 through 12, page 15 of this manual for proper installation. = Combustion Air / = Venting) Figure 14 - Chimney Venting with Outside Air Single Wall = Combustion Air /...
7 - GAS SUPPLY PIPING Figure 15 Manual Main Gas Shutoff Valve CAUTION Outside Boiler Jacket WHAT TO DO IF YOU SMELL GAS With Manufacturer Suggested Piping With Drip Leg • Do not try to light any appliance. • Do not touch any electrical switch; do not use any phone in your building.
8 - ELECTRICAL CONNECTIONS Figure 16 - Terminal Block WARNING Electrical shock hazard. Turn OFF electrical power supply at service panel before making electrical connections. Failure to do so could result in death or serious injury. 8.1 General Electrically bond boiler to ground in accordance with requirements of authority having jurisdiction.
9 - START UP PROCEDURE 9.1 Fill Boiler With Water And Purge Air WARNING NOTICE Asphyxiation hazard. Carbon monoxide is odorless, To maintain boiler ef ciency and prevent boiling tasteless, clear colorless gas, which is highly toxic. inside the heat exchanger, ush entire heating Carbon monoxide production shall not exceed system until clean.
Page 25
9 - START UP PROCEDURE 9.6 Check Combustion Figure 17 - Test Ports Natural Gas Vent Gases Measure input. English unitsTurn off gas to all other Test Port appliances. • Activate some heating zones to dissipate heat. • Set boiler on high re. •...
10 - OPERATING INSTRUCTIONS WARNING CAUTION If you do not follow these instructions WHAT TO DO IF YOU SMELL GAS exactly, a fi re or explosion may result • Do not try to light any appliance. causing property damage, personal injury •...
10 - OPERATING INSTRUCTIONS 10.3 Checks During Operation 10.5 Indicator During Operation • Check for leaks in piping systems. Correct immediately Heating if found. Call for heat (generated by Room Thermostat) is indicated • Check the ef ciency of the ue gases and combustion by hot air ashing above radiator symbol on the control.
10 - OPERATING INSTRUCTIONS Boiler Ignition Summer/Winter Switchover Supply unit with electricity. Press the button for 2 seconds. Display will activate Summer symbol (see item 10 on the control panel display). Boiler will deliver tap water only. Boiler ignition Antifreeze system stays on. For 120 seconds display will show FH which identi es the To turn off Summer mode, press button again for 2 air venting cycle for the heating system.
Page 29
10 - OPERATING INSTRUCTIONS ECO/COMFORT selection The unit has a function that ensures a high domestic hot water delivery speed and maximum comfort for the user. When the device is activated (COMFORT mode), the water contained in the boiler remains hot, ensuring faster availability of domestic hot water.
Page 30
10 - OPERATING INSTRUCTIONS Compensation curve and curve offset Press the button (see item 6 on the control panel display) for 5 seconds once to display the actual compensation curve, which can be modi ed with the DHW buttons (see items 1 and 2 on the control panel display).
Page 31
10 - OPERATING INSTRUCTIONS Example of parallel compensation curve shift Press the button (see item 6 on control panel display) for 5 seconds again to exit parallel curve adjustment mode. If the room temperature is lower lower than the required value, it is advisable to set a higher order curve and vice versa.
Page 32
10 - OPERATING INSTRUCTIONS Water system pressure adjustment The lling pressure with system cold, read on the boiler water gauge, must be approximately 11 psi. If the system pressure falls to values below minimum, the boiler control will activate fault F37. Low system pressure fault Once the system pressure is restored, the boiler will activate the 120-second air venting cycle indicated on the...
11 - GENERAL MAINTENANCE AND CLEANING 11.1 Beginning of Each Heating Season 11.2 Annual Shut Down Procedure • Check boiler area is free from combustible materials, • Follow instructions “To Turn Off Gas To Appliance” unless gasoline, and other ammable vapors and liquids. boiler is also used to supply domestic hot water.
12 - RATINGS AND CAPACITIES Data Unit CCB150 Boiler category Category I - III Type of Gas Natural Gas Btu/hr 150000 Maximum Input 0-2000 Ft Btu/hr 135000 Maximum Input 2000-4500 Ft 39.6 Btu/hr 50000 Minimum Input 0-2000 Ft 14.6 Btu/hr 45000 Minimum Input 2000-4500 Ft 13.2...
Page 35
(1)(3) Maximum Minimum (MBH) (1)(2) CCB-150 85.0 1000 Btu/hr (British Thermal Units Per Hour) Heating Capacity and AFUE (Annual Fuel Utilization Effi ciency) are based on DOE (Department of Energy) test procedures. Net AHRI Ratings based on piping and pickup allowance of 1.15. Contact Technical Support before selecting boiler for installations having unusual piping and pickup requirements, such as intermittent system operation, extensive piping systems, etc.
Page 36
12 - RATINGS AND CAPACITIES Diagrams Pressure - power diagrams wc CCB 150 13 14 15 16 17 18 19 20 21 22 23 24 25 26 27 28 29 30 31 32 33 34 35 36 37 38 39 40 41 42 44 45 A LPG B NATURAL GAS Losses of load / head of circulators...
13 - TROUBLE SHOOTING Diagnostics The boiler is equipped with an advanced self-diagnosis system. In case of a boiler fault, the display will ash indicating the fault code. There are faults that cause permanent shutdown (marked with the letter “A”): to restore operation just press the RESET button (detail 6 - Section 10.4, Control, page 25) for 1 second or RESET on the optional remote timer control if installed;...
WIRING DIAGRAM 370 - Field Source LWCO 138 - Optional Outdoor Sensor 120Vac 60Hz DBM34 + 15V G N D O U T + 5 V Important: Before connecting the room thermostat, remove the jumper on terminal block. 16 Modulating fan 114 Water pressure switch 32 Heating circulating pump 136 Flow meter...
REPAIR PARTS LIST Part Number Description FE3980B990 CASING "CTR"...
Page 40
REPAIR PARTS LIST Part Number Description FE3980C200 KIT CONTROL BOX FE3980B850 KIT CONTROL BOARD DBM34 FE3980C210 KIT FRONT COVER "CTR" FE3980B840 KIT PRESS.TEMP. GAUGE FE3980C330 KIT WIRING FE3980C220 KIT MONO CABLE EL.
Page 44
REPAIR PARTS LIST Part Number Description FE3980B930 KIT GASKETS SET FE3980C090 PRESSURE TEST POINT "VENTURI" FE3980C100 FAN GASKET FE3980B940 FE3980C110 COMBUSTION CHAMBER INSULATION FE3980C120 IGNITION ELECTRODE FE3980C130 BURNER 17 R.m. FE3980B960 GAS VALVE VGU 54S FE3980C140 17 INJECTOR 1.35mm NG FE3980C150 17 INJECTOR 0.85mm LP FE3980C160...
DIMENSIONS Figure 1 - Dimensions Vue d'en haut Vue latérale Vue de face Vue de dos 1 = 1” MPT Eau d'alimentation vers l'installation de chauffage (sortie) 2 = 3/4” MPT Sortie d'eau du robinet 3 = 3/4” FPT Arrivée de gaz 4 = 3/4”...
Page 48
INDEX 1 - Introduction ......................... 49 2 - Informations importantes sur la sécurité ................50 3 - Vue d'ensemble et principaux éléments ................51 4 - Emplacement de la chaudière ..................54 5 - Tuyauterie hydronique ....................56 6 - Tuyauterie de l'air de combustion et d'évent - Catégorie I (cheminée) ........60 6 - Tuyauterie d'air de combustion et de ventilation directe de catégorie III .......
Informations et spécifi cations publiées dans ce manuel en vigueur au moment de son impression. ECR International, Inc. se réserve le droit de mettre fi n, de modifi er les spécifi cations ou la conception de l'installation à tout moment, sans...
2 - INFORMATIONS IMPORTANTES SUR LA SÉCURITÉ 2.1 Généralités 2.3 L'installation doit être conforme aux critères L'installation de la chaudière doit être effectuée par un établis par l'organisme compétent ou, en l'absence installateur compétent. Consultez le glossaire pour plus de tels critères : d'informations.
3 - VUE D'ENSEMBLE ET PRINCIPAUX ÉLÉMENTS Figure 2 Liste des éléments...
Page 52
3 - VUE D'ENSEMBLE ET PRINCIPAUX ÉLÉMENTS Réf. pièce Description Chambre hermétique Arrivée de gaz Sortie d'eau chaude sanitaire (ECS) Arrivée d'eau chaude sanitaire (ECS) Système d'alimentation Retour installation Ventilateur modulable Chambre de Combustion Groupe brûleur Brûleur Isolation de la Chambre DEcombustion Échangeur de Chaleur en cuivre Collecteur d'échappement Sortie Collecteur D'échappement...
Page 53
3 - VUE D'ENSEMBLE ET PRINCIPAUX ÉLÉMENTS AVERTISSEMENT Risque d'incendie, d'explosion, d'asphyxie et d'électrocution. Coupez l'alimentation électrique, de gaz au niveau de la vanne d'arrêt avant de tenter de déposer la jaquette de la chaudière. Le non-respect de ces instructions peut causer de graves lésions ou la mort.
4 - EMPLACEMENT DE LA CHAUDIÈRE 4.1 Remarques sur l'emplacement de la Figure 5 - Dégagements de la chaudière chaudière • Température ambiante toujours supérieure à 0°C (32°F) pour éviter de geler. • Chaudière homologuée pour l'installation dans des placards. •...
4 - EMPLACEMENT DE LA CHAUDIÈRE Fourniture en amont des tuyaux et Figure 6 - Support de montage mural raccordements d'eau de retour avec accessoires d'usine avant le montage mural. 2,4 cm 2,4 cm 4.3 Montage mural ”) ”) Montez la chaudière sur un mur à l'aide du support de montage mural fourni avec l'appareil.
5 - TUYAUTERIE HYDRONIQUE 5.1 Généralités Les produits chimiques de traitement doivent assurer une désoxygénation complète de l'eau et contenir des agents de • Posez la tuyauterie conformément aux normes établies par protection spéci ques pour les métaux jaunes (cuivre et ses l'organisme compétent.
5 - TUYAUTERIE HYDRONIQUE Figure 7 - Soupape de sécurité et évent AVERTISSEMENT d'air (vue de face à la chaudière) Risque de brûlure et d'ébouillantage. La soupape de sécurité peut libérer de la vapeur ou de l'eau chaude pendant le fonctionnement. Installez la tuyauterie d'évacuation conformément à...
Page 58
5 - TUYAUTERIE HYDRONIQUE Figure 8 - Tuyauterie d'évacuation de la soupape de sécurité Soupape de sécurité Vanne d'arrêt de gaz en position ouverte Consultez la règlementation en vigueur pour la distance maximale par rapport au sol...
6 - TUYAUTERIE DE L'AIR DE COMBUSTION ET D'ÉVENT - CATÉGORIE I (CHEMINÉE) B. elles sont doublées avec un tuyau d'évent de type B AVERTISSEMENT L'installation de la chaudière et de l'évacuation C. Utilisez une gaine d'évent exible doit être effectuée par un installateur compétent, D.
6 - TUYAUTERIE D'AIR DE COMBUSTION ET DE VENTILATION - CATÉGORIE I (CONDUIT DE CHEMINÉE) 6.2 Dégagement minimum du tuyau d'évent Tout fonctionnement incorrect du système d’évent commun doit être corrigé de sorte que l’installation soit conforme au Code • Utilisez le tuyau d'évent de type B en le faisant passer par le national de gaz combustible ANSI Z223.1/NFPA 54 et/ou au Code vide sanitaire.
à au moins 1,2 m (4 pieds), et en l'évacuation à travers des murs combustibles. La aucun cas au-dessus ou au-dessous, sauf si une terminaison d'évent ECR, 5612601 est une terminaison distance horizontale de 1,2 m (4 pieds) est maintenue, d'évent direct certi ée (pour l'évacuation de catégorie par rapport à...
6 - TUYAUTERIE D'AIR DE COMBUSTION ET DE VENTILATION DIRECTE DE CATÉGORIE III Si l'évent horizontal doit traverser un vide sanitaire ou tout AVERTISSEMENT autre espace non chauffé, les températures roides peuvent Le prolongement de l'évent vers l'extérieur ne doit gaz de provoquer une condensation continue des combustion...
6 - TUYAUTERIE D'AIR DE COMBUSTION ET DE VENTILATION Assurez l'arrivée d'air de combustion et d'air de ventilation • Tout l'air extérieur. Assurez des ouvertures conformément à la section « Air pour la Combustion et la permanentes sur l'extérieur directement ou à travers ventilation »...
Page 65
6 - TUYAUTERIE D'AIR DE COMBUSTION ET DE VENTILATION Figure 11 - Dégagements pour l'évacuation horizontale AVIS Maintenez une distance de 12” (30 cm) US, 18” Figure 12 - Ventilation à deux tuyaux (46 cm) Canada au-dessus de la limite de neige supérieure ou du sol.
Page 66
6 - TUYAUTERIE D'AIR DE COMBUSTION ET DE VENTILATION AVIS Figure 13 - Ventilation de la cheminée avec air ambiant simple paroi Consultez la section 6.1, paragraphes 3 à 12, page 15 de ce manuel pour une installation correcte. = Air de combustion / = Ventilation) Figure 14 - Ventilation de la cheminée avec air extérieur simple paroi...
7- TUYAUTERIE D'ALIMENTATION DE GAZ Figure 15 Vanne d'arrêt de gaz principale ATTENTION manuelle en dehors de la jaquette de la chaudière QUE FAIRE EN CAS D'ODEUR DE GAZ Tuyauterie avec collecteur de sédiments suggérée par le • Ne tentez pas d'allumer un quelconque appareil. fabricant •...
8 - BRANCHEMENTS ÉLECTRIQUES AVERTISSEMENT Figure 16 - Bornier Risque d'électrocution. Coupez l'alimentation électrique sur le tableau de service avant d'effectuer des connexions électriques. Le non-respect des ces instructions peut causer de graves lésions et la mort. 8.1 Généralités Reliez la chaudière à la terre conformément aux spéci cations de l'organisme compétent.
9 - PROCÉDURE DE DÉMARRAGE 9.1 Remplissage de la chaudière avec de l’eau et AVERTISSEMENT purge d’air Risque d'asphyxie. Le monoxyde de carbone est un AVIS gaz inodore, insipide, clair et incolore, hautement Pour préserver l’ef cacité de la chaudière et prévenir toxique.
9 - PROCÉDURE DE DÉMARRAGE 9.6 Contrôle de la combustion Figure 17 - Ports de test Gaz naturel Port de test Mesurez l'entrée. Mesures anglaises Fermez le gaz des gaz de tous les autres appareils. d'évent • Activez quelques zones de chauffage pour dissiper la chaleur.
10 - INSTRUCTIONS D'UTILISATION AVERTISSEMENT CAUTION Le non-respect de ces instructions peut QUE FAIRE EN CAS D’ODEUR DE GAZ exposer à un incendie ou une explosion • Ne tentez pas d’allumer un quelconque appareil. susceptible d’entraîner des dommages • Ne touchez aucun interrupteur électrique ; matériels, des lésions corporelles, voire n’utilisez aucun téléphone dans votre bâtiment.
10 - INSTRUCTIONS D'UTILISATION 10.3 Contrôles pendant le fonctionnement 10.5 Indicateur pendant le fonctionnement • Véri ez s’il y a des fuites dans les systèmes de tuyauterie. Chauffage Réparez-les immédiatement le cas échéant. • Véri ez l’ef cacité des conduits de gaz de combustion et d’air L’appel de chaleur (généré...
10 - INSTRUCTIONS D'UTILISATION Allumage de la chaudière Commutation été/hiver Mettez l’appareil sous tension. Appuyez sur le bouton pendant 2 secondes. L’af cheur active le symbole Été (voir le repère 10 sur l’af cheur du tableau des commandes). La chaudière distribue Allumage de la chaudière de l’eau du robinet uniquement.
10 - INSTRUCTIONS D'UTILISATION Sélection ECO/CONFORT L’appareil est doté d’une fonction qui garantit une vitesse élevée de distribution d’eau chaude sanitaire et un confort optimal pour l’utilisateur. Lorsque le dispositif est activé (mode CONFORT), l’eau dans la chaudière reste chaude, garantissant une disponibilité...
10 - INSTRUCTIONS D'UTILISATION Courbe de compensation et décalage de la courbe Appuyez une fois sur le bouton (voir le repère 6 sur l’af cheur du tableau des commandes) pendant 5 secondes pour af cher la courbe de compensation réelle, qui peut être modi ée avec les boutons ECS (voir les repères 1 et 2 sur l’af cheur du tableau des commandes).
Page 76
10 - INSTRUCTIONS D'UTILISATION Exemple de décalage parallèle de la courbe de compensation Appuyez de nouveau sur le bouton (voir le repère 6 sur l’af cheur du tableau des commandes) pendant 5 secondes pour sortir du mode de réglage de la courbe parallèle. Si la température ambiante est inférieure à...
10 - INSTRUCTIONS D'UTILISATION Réglage de la pression d’eau de l’installation La pression de remplissage avec l’installation froide mesurée par l’indicateur de niveau d’eau doit être d’environ 11 psi. Si la pression de l’installation chute à des valeurs au-dessous du minimum, la commande de la chaudière active l’erreur F37.
11 - ENTRETIEN GÉNÉRAL ET NETTOYAGE 11.1 Début de saison de chauffage 11.2 Procédure d'arrêt annuelle • Contrôlez que la surface de la chaudière soit exempte de • Suivez les instructions pour « Couper l'alimentation en matériaux de combustible, de gasoil et de toute autre gaz de l'appareil »...
12 - RENDEMENTS ET CAPACITÉS Données Unité CCB150 Catégorie de chaudière Catégorie I - III Type de gaz Gaz naturel Btu/h 150000 Entrée maximum 0 - 2000 pieds (0 - 610 m) Btu/h 135000 Entrée maximale 2000-4500 pieds (610 - 1 372 m) 39,6 Btu/h 50000...
Maximum Minimum (MBH) (1)(2) (1)(3) CCB-150 85,0 1 000 Btu/h (unités thermiques britanniques par heure) La capacité de chauffage et l'effi cacité de l'utilisation annuelle de combustible (AFUE) reposent sur les procédures de test du Ministère de l'Énergie. Rendements AHRI nets basés sur une tolérance pour la tuyauterie et la collecte de 1.15. Contactez l'Assistance technique avant de choisir la chaudière pour Installations ayant des spécifi...
13 - PANNES Diagnostic La chaudière est équipée d'un système d'autodiagnostic sophistiqué. En cas de dysfonctionnement de la chaudière, l'écran clignote et af che le code d'erreur. Certaines anomalies provoquent l'arrêt permanent (signalées par la lettre « A ») : pour rétablir le fonctionnement, appuyez simplement sur le bouton RESET (détail 6 - Section 10.4, Commande, page 25) pendant 1 seconde ou RESET sur la télécommande de temporisation, si installée ;...
SCHÉMA DE CÂBLAGE 370 - Interrupteur niveau d'eau bas installé sur place 138 - Capteur extérieur en option 120Vac 60Hz DBM34 + 15V G N D O U T + 5 V Important : Avant de raccorder le thermostat d'ambiance, enlevez le cavalier sur le bornier. Repère 16 Ventilateur modulable 114 Commutateur pression d'eau...
LISTE DES PIÈCES DÉTACHÉES CODE Réf. Description Qté FE3980B990 ENVELOPPE « CTR »...
Page 85
LISTE DES PIÈCES DÉTACHÉES CODE Réf. Description Qté FE3980C200 KIT BOÎTIER DE COMMANDE FE3980B850 KIT PANNEAU DE COMMANDE DBM34 FE3980C210 KIT COUVERCLE AVANT « CTR » FE3980B840 KIT INDICATEUR DE PRESSION ET DE TEMPÉRATURE FE3980C330 KIT CÂBLAGE FE3980C220 KIT MONO CABLE ÉL.
Page 89
LISTE DES PIÈCES DÉTACHÉES CODE Réf. Description Qté FE3980B930 KIT JEU DE JOINTS FE3980C090 POINT DE TEST DE PRESSION « VENTURI » FE3980C100 JOINT DE VENTILATEUR FE3980B940 VENTILATEUR FE3980C110 ISOLATION DE LA CHAMBRE DE COMBUSTION FE3980C120 ÉLECTRODE D'ALLUMAGE FE3980C130 BRÛLEUR 17 R.m. FE3980B960 VANNE À...