O & M Manual IM05805023K
Effective: June 2012
INSTALLATION & MAINTENANCE MANUAL FOR
JOCKEY PUMP CONTROLLERS
In order to familiarize yourself with the Jockey Pump
Controller, please read the instruction manual thoroughly
and carefully. Retain the manual for future reference.

1. Installation and Mounting of the Controller

Carefully unpack the controller and inspect thoroughly.
It is recommended that the controller is located as close as
is practical to the motor it controls
The controller is not free standing and must be bolted
securely to a wall. For dimensional and weight data please
refer to the respective data sheets for the Jockey Pump
Controller.
2. System Pressure Connection
The Jockey Pump Controller is equipped with a Pressure
Transducer. The controller is provided with a ¼" NPT
female system pressure connection located on the bottom,
external side of the enclosure. The connection should be
installed as per NFPA, pamphlet No. 20.
NOTE: Water lines to the pressure transducer must be free
from dirt and contamination.
The pressure should not exceed what the pressure
transducer is rated for.

3. Electrical Connections

All electrical connections should meet national and local
electrical codes and standards.
The controller should be located or so protected that they
will not be damaged by water escaping from pumps or
pump connections. Current carrying parts of controllers
shall be a minimum of 12 inches (305 mm) above the floor
level.
Prior to starting verify all data on the nameplate such as,
catalog number, AC line voltage and horsepower.
EATON CORPORATION
Inspect all electrical connections, components and wiring
for any visible damage and correct as necessary. Ensure
that all electrical connections are tightened before
energization.
Install necessary conduit using proper methods and tools.
Incoming AC line voltage is clearly marked L1, L2, L3 and
ground, located at the top of the breaker.
www.chfire.com
EATON XTJP / XTJY
Jockey Pump Controllers
Page 3