THINGS TO CHECK BEFORE INSTALLATION
Does the output (kW) match the volume (ft³/m³) of the sauna
room? See Table 1.
In case there are any uninsulated brick, tile or glass walls in the
sauna room, an additional volume of 53 ft³ (1.5 m³) should be
added to the sauna room for each such square meter of the wall.
The suitable output of the heater will be determined based on
that volume according to Table 1.
The producer's warranty guarantee is invalid if the heater and
sauna room have been dimensioned incorrectly!
Minimal safe distances between the sauna room's ceiling and
walls to consider in installing the electric heater are listed in Table
2.
INSTALLATION
Positioning the heater
The heater must be positioned in such a way that there is a safe
distance between flammable materials and the heater.
The heater must be installed in a way that prevents people
from having physical contact with the heater or that dangerous
situations could emerge during the heating process.
The heater holds approximately 595 lb (270 kg) of stones.
The inputs of the power cable are on the bottom cover of the
heater.
Output
Table 1
kW
(240V)
HIVE 6
6
HIVE 9
9
HIVE 10.5
10.5
4
Room
Elements
kW (240V)
176.6-282 ft
3
5-8 m
3
317.8-530 ft
3
9-15 m
3
353.1-706.3 ft
3
10-20 m
3
Amps
Circuit Breaker
A
2
25
3
37,5
3
43,75
Wire
size
A
AWG
30
10
50
8
50
6