OPTIMA-EX
An example of the label used for the certified plug is shown below:
Via Costa Erta 15 Parre BG ITALY
218.EX3237
IMQ 11 ATEX 011
Ex tb IIIC Db IP66
T90°C Ta -25 +60°C
3P+N+
32A - 6h 346-415V~
READ THIS DOCUMENT CAREFULLY PRIOR TO THE INSTALLATION
Recipients: expert electricians or duly trained personnel.

1. SAFETY INFORMATION

The mobile plugs of the OPTIMA-EX Series are used for installations in environments with a potential risk of explosion due to the
presence of combustible dust classified as Zone 21.
These installation, use and maintenance instructions must be kept in a safe place for future reference. During operation or
maintenance work on the device, do not leave this manual or other objects inside the enclosure.
Use the mobile plugs of the OPTIMA-EX Series for their approved use only, and keep them fully intact and perfectly clean.
The mobile plugs have been designed to withstand shocks of 7J, and to be used under normal vibration conditions.
They have not been designed for use in environments subject to extreme vibrations.
The type of protection cannot be guaranteed if the product is not installed correctly.
Use only original spare parts supplied by SCAME.
No modification/work is allowed on the mobile plug unless specifically indicated in this manual.
DO NOT OPEN THE ENERGIZED ENCLOSURE IN PRESENCE OF AN EXPLOSIVE ATMOSPHERE.
DO NOT SEPARATE WHEN ENERGIZED.
Always comply with national accident-prevention rules and with the safety instructions contained in this manual whenever you
work on the mobile plug.

2. COMPLIANCE WITH STANDARDS

The mobile plugs of the OPTIMA-EX series are intended for use in Zone 21 (EN 60079-0:2012+A11:2013 EN 60079-31:2014).

3. TECHNICAL DATA

3.1 TYPE OF EX PROTECTION
II 2D Ex tb IIIC T90°C Db IP66
Ta -25/+60°C
Year xxxx: Year of manufacture.
Product suited for use in explosive atmosphere.
II: Product classified as belonging to group II, installable in above-ground systems.
2D: Product classified as belonging to category 2 for environments featuring the presence of combustible dust (D) suited for
installation in Zone 21.
MP36517
2011
0051
II 2D
Details of the adhesive label.
10
ZP90755-8