Level 2
Password =
2001
2.1 External CT ratio
Ct =
External CT primary/secondary ratio
External CT ratio (Ct): 1...9999
(maximum primary current 50000/5A)
On modifying the ratios the power counters are automatically reset.
07/17 10783591 WEB E cod.MFD4E06
(e.g. CT 800/5A Ct = 160)
Phase sequence diagnostic
In the software there is a diagnostic and correction algorithm of the voltmetric and ampero-
metric connection sequence.
The function can be activated on request and password protected: it can display and edit the
wiring sequence with the following limitations:
1) The neutral conductor
(in the 4-wire wirings)
2) There must not be any crossings between the currents
3) The power factor must be between 0.9cap and 0.7ind for each phase
See www.imeitaly.com "TECHNICAL
Nemo D4-e
must be correctly positioned
(terminal 11)
SUPPORT".
5