Electric Defrost Timer (Freezers)
•
The defrost timer clock must be set to the correct time at initial start-up and after any power interruptions.
•
Set the clock by rotating the clock face until the correct time is at the arrow on the face of the timer.
•
The switch is programmed by pushing the captive trippers to the inner ring for the entire period the load is to be
turned "ON".
•
When a tripper is pushed to the outside, the switch is in the "DEFROST" position.
•
Each defrost tripper represents 15 minutes of defrost time.
•
The timer is factory set for four defrost cycles daily at the following times: 4:00AM, 10:00AM, 4:00PM, and
10:00PM. Each defrost cycle is programmed for 30 minutes duration.
•
The defrost times can be changed to initiate at periods of low activity.
•
A setting of two to four defrost cycles per day is typical. For heavier frost loads, additional cycles may be required.
•
The timer starts the defrost cycle automatically at the predetermined times.
NOTE: If the defrost termination thermostat fails to close, the fail safe setting on the timer will terminate the defrost cycle.
When the defrost cycle begins:
•
The compressor and evaporator fan motors will stop.
The evaporator coil heaters will activate and increase the coil temperatures above 32°F/0°C, melting the frost and ice.
•
•
NOTE: Walk-in temperatures will elevate above the set point during defrost cycles (30 minutes, 4 times per day)
but will return to the set point once the defrost cycle is complete.
•
When the defrost time is complete or the evaporator coil warms to approximately 55°F/13°C, the compressor will
start the refrigeration cycle but the evaporator fan(s) will remain idle until the evaporator coil temperature is at or
below freezing.
•
Once the evaporator coil temperature reaches approximately 30°F/-1°C, the evaporator fan(s) will activate.
•
The system operates in the refrigeration cycle until another defrost cycle is initiated by the timer.
Air Defrost Timer (Coolers)
•
The defrost timer is incorporated into the Air Defrost Thermostat. There is no separate Air Defrost Timer.
•
The defrost timer is factory set for four defrost cycles daily at the following times: 4:00AM, 10:00AM, 4:00PM, and
10:00PM. Each defrost cycle is programmed for 30 minutes duration.
•
The defrost times can be changed to initiate at periods of low activity.