Sensor Offset Adjustment (So) Sensor offset allows you to compensate for any difference between the displayed
temperature value and the temperature sensed at the A99 sensor. Select a temperature value to offset the
temperature displayed on the LCD from the temperature sensed at the sensor. The sensor offset adjustment range is
from -5°F to 5°F (-3°C to 3°C) in 1° increments.
•
Backlight Brightness Level (bLL) The backlight brightness level feature allows you to adjust the LCD backlight intensity.
At level 0 the backlight is off. Level 10 is the brightest backlight setting and the system default. The selected backlight
brightness level is applied to the LCD during normal operation. When you enter the programming menus to set up the
control or press any key, the LCD automatically goes to the brightest level. If you do not press a key for 30 seconds, the
main screen displays and the backlight setting reverts to the selected brightness level.
Standard parameter setup codes, descriptions, range of values, and default values
Parameter code
Un
OFF
On
ASd
tSb
So
HtS
LtS
SF
bLL
dFt
dI
SdF
bIn
1 The default values for general application A421 models are shown. OEM A421 models may have different default values.
Parameter description
(menu)
Temperature Units
(Advanced only)
Relay Off Temperature
(Basic, Advanced, and
Restricted)
Relay On Temperature
(Basic and Advanced)
Anti-Short Cycle Delay
(Basic and Advanced)
Temperature Setback
(Advanced only)
Sensor Offset Adjustment
(Advanced only)
High Temperature Stop
(Advanced only)
Low Temperature Stop
(Advanced only)
Sensor Failure Action
(Basic and Advanced)
LCD Backlight Brightness
Level Adjustment
(Advanced only)
Defrost Cycle Time
(Advanced only)
Defrost Interval
(Advanced only)
Start or Stop Defrost Off-
Cycle (Advanced only)
Binary Input Mode
(Advanced only)
Range of usable values
ºF or ºC
-40ºF to 212ºF (-40ºC to
100ºC)
-40ºF to 212ºF (-40ºC to
100ºC)
0 minutes to 12 minutes
-50ºF to 50ºF (-30ºC to
30ºC)
-5ºF to 5ºF (-3ºC to 3ºC)
-40ºF to 212ºF (-40ºC to
100ºC)
-40ºF to 212ºF (-40ºC to
100ºC)
0 = output relay
deenergized
1 = output relay energized
0 to 10; 0 = backlight off,
10 = brightest backlight
setting
1 minutes to 99 minutes
0 or 2 hours to 24 hours
Change 0 to 1 to Start a
new Defrost Cycle Change
1 to 0 to Stop a Defrost
Cycle
0 = Temperature Setback
Mode 1 = Start Defrost
Cycle Mode
Factory default value
1
ºF
25ºF
30ºF
1 minute
0ºF
0ºF
212ºF
-40ºF
1 output relay energized
10 (brightest backlight)
30 minutes
8 hours
0
1