Electrical Mounting; Requirements For Electrical Connection - WIKA PSD-4-ECO Mode D'emploi

Pressostat oem avec afficheur
Table des Matières

Publicité

Les langues disponibles

Les langues disponibles

5. Commissioning, operation
Sealing variants
Parallel threads
Seal the sealing face  with flat gasket,
lens-type sealing ring or WIKA profile
sealing.
Tapered threads
Wrap threads with sealing material
(e.g. PTFE tape).

5.4 Electrical mounting

5.4.1 Requirements for voltage supply
→ For power supply see product label
The power supply for the pressure switch must be made via an energy-limited electric circuit in accordance with
section 9.4 of UL/EN/IEC 61010-1, or an LPS per UL/EN/IEC 60950-1 / CSA C22.2 no. 60950-1, or class 2 in
accordance with UL1310/UL1585 (NEC or CEC). The voltage supply must be suitable for operation above 2,000 m
should the pressure switch be used at this altitude.

5.4.2 Requirements for electrical connection

Ingress protection of the mating connector corresponds to the ingress protection of the pressure switch.
Cable diameter matches the cable bushing of the mating connector.
Cable gland and seals of the mating connector are correctly seated.
No humidity can ingress at the cable end.
WIKA operating instructions, model PSD-4-ECO
per EN 837
NPT, R and PT
per DIN EN ISO 1179-2
(formerly DIN 3852-E)
EN
13