The device can be used by children 8
years or older and by persons with
physical, sensory or mental impairments,
or by people without any experience or
the necessary knowledge, provided they
are
supervised
instructions regarding the safe use of the
device and provided they have a
thorough understanding of the associated
risks.
Children must be supervised to ensure
they do not play with the device.
Cleaning and maintenance must never
be performed by children unless they are
properly supervised.
The room must be properly ventilated
when the cooker hood is used at the
same time as other combustion devices,
gas or otherwise.
The hood must be regularly cleaned both
internally and externally (AT LEAST
ONCE
PER
accordance
with
instructions.
Failure to follow the rules for hood
cleaning and filter replacement and
cleaning shall result in a fire hazard.
It is strictly prohibited to flame food.
The use of an open flame may damage
the filters and cause a fire hazard; it must
therefore
be
circumstances.
Extra care must be taken when frying to
prevent the oil from overheating and
catching fire.
CAUTION: When the hob is on, the
accessible parts of the hood may
become hot.
or
have
received
MONTH),
in
the
maintenance
avoided
under
Caution! Do not connect the device to
the electrical network until installation is
entirely complete.
In regards to the technical and safety
measures that must be adopted for fume
extraction, regulations issued by local
authorities must be strictly followed.
The extracted air must not be conveyed
through the same ducts used to extract
the fumes generated by gas combustion
or other types of combustion devices.
Never use the hood unless the grill has
been correctly assembled!
Use only the fastening screws supplied
with the product for its installation, or if
not supplied, purchase the correct type of
screws. Use screws with the right length,
as indicated in the installation guide.
When the cooker hood is used together
strict
with other devices powered with non-
electrical energy, the negative pressure
of the room must not exceed 4 Pa (4 x
10-5 bar).
all
53