Jung eNet FM AS 816 REG Instructions D'utilisation page 14

Actionneur tor / volet roulant 8 / 4 voies, modulaire
Table des Matières

Publicité

Les langues disponibles

Les langues disponibles

eNet
Actionneur TOR / volet roulant 8 / 4 voies, modulaire
Switch­on on brightness un­
dershoot
Invert switching output
Minimum switching repeat
time
Operating hours
Settings, "Venetian blind" channel
Parameters
Manual commissioning
82581913
J:0082581913
On, Off
Basic setting: Off
On, Off
Basic setting: Off
100 ms ... 10 sec
Basic setting: 100 ms
0...65535
Basic setting: Current value
Setting options, Basic set­
ting
On, Off
Basic setting: On
14/18
Allows automatic switch­on
according to the brightness. If
the parameter is On, then the
light controller switches on au­
tomatically when the bright­
ness setpoint is greatly under­
shot. We recommend only
using the parameter in
connection with the parameter
"Switch­off on brightness over­
shoot". This parameter is not
yet active, as a light controller
has not yet been implemen­
ted.
Inverts the switching output
from NO contact function (fac­
tory setting) to NC contact
function
Limits the switching speed of
the device by increasing the
value, in order to protect the
load, for example. Only when
the set time has elapsed is
switching possible again. The
last command during the blo­
cking time is executed after a
delay. The switching repeat
time starts after each swit­
ching operation.
The time is counted during
which the load is physically
switched on (relay contact clo­
sed).
This parameter can be reset to
"0", for example after exchan­
ging the load.
The Reset button is used to
reset the counter to "0". The
device must be programmed
to apply the change.
Explanations
Blocks manual commissioning
for the device channel. In the
"Off" setting, the device can­
not be reset to the factory set­
ting.
13.03.2014