Manual switchoff of the run
on time
Switchon delay
Switchoff delay
Runon time
Behaviour after the end of the
disabling function
82581913
J:0082581913
On, Off
Basic setting: Off
0 s ... 24 h
Basic setting: 0 s
0 s ... 24 h
Basic setting: 0 s
0 s ... 24 h
Basic setting: 0 s
On
Off
no change
Last value
Basic setting: No change
12/18
Allows manual switchoff of a
running runon time. If the pa
rameter is switched off, then a
switchoff command will also
switch the actuator on. This
parameter is directly connec
ted to the "Runon time" para
meter.
The load switches on after a
delay. Repeated switchon
commands restart the delay
time. If the load has not yet
been switched on due to the
delay when a switchoff com
mand comes, then the load
will remain off.
In Flashing operating mode,
the pause times are set using
this parameter.
Note: The set time apply to
operation using radio transmit
ters. The device is switched
immediately when the Prog
button is pressed.
The load switches off after a
delay. Repeated switchoff
commands restart the delay
time. If the load has not yet
been switched off due to the
delay when a switchon com
mand comes, then the load
will remain on.
In Flashing operating mode,
the pulse times are set using
this parameter.
Note: The set time apply to
operation using radio transmit
ters. The device is switched
immediately when the Prog
button is pressed.
As soon as a runon time has
been entered, the actuator will
no longer remain on perma
nently, but only for the length
of the runon time. The runon
time is restarted if actuation is
repeated. This parameter is di
rectly connected to the "Ma
nual switchoff of runon time"
parameter.
Note: The set time apply to
operation using radio transmit
ters. The device is switched
immediately when the Prog
button is pressed.
Behaviour of the output when
a block is removed.
13.03.2014