eNet
Actionneur TOR / volet roulant 8 / 4 voies, modulaire
Channel 4, 8
Settings, "Switching" channel
Parameters
Manual commissioning
Operating mode
Local Operation
82581913
J:0082581913
Switching, shutter/blind
Basic setting: Venetian blind
Setting options, Basic set
ting
On, Off
Basic setting: On
Switching
Buttons
Flashing
Continuous on
Continuous off
Basic setting: Switching
On, Off
Basic setting: On
11/18
Specifies whether Channels 4
and 8 work as switching or Ve
netian blind outputs.
Explanations
Blocks manual commissioning
for the device channel. In the
"Off" setting, the device can
not be reset to the factory set
ting.
Switching
After switchon, the device re
mains stable in the "On" state,
and stable in the "Off" state af
ter switchoff.
Buttons
The device switches "On"
when any channel button of a
radio transmitter is pressed
and "Off" when the button is
released. It is irrelevant whe
ther the "On" or "Off" channel
button is pressed.
Flashing
Switchon starts flashing and
switchoff stops flashing. The
default flash frequency is 1
Hz. This frequency is also the
maximum flash frequency.
The flash frequency can be
changed using parameters.
The parameter "Switchoff de
lay" is used for the pulse time
and the parameter "Switchon
delay" for the pause time.
Continuous on
The output switches to conti
nuously "On". All operations of
radio transmitters and the
Prog button are ignored.
Continuous off
The output switches to conti
nuously "Off". All operations of
radio transmitters and the
Prog button are ignored.
Blocks the output for operation
using the Prog button.
13.03.2014