CombiPower
6
Configuring the device with the
remote control
6.1
Overview of parameters
NOTE
I
For the menu and parameter structure, see fig. 4, page 4.
Access to the "Another Param" menu is password-protected.
This menu can only be accessed by technicians.
"Change Run Mode" menu (operating mode)
Parameter
COMBI Power On
CHR Power On
"P.S. Mode Param" menu (power sharing mode)
Parameter Explanation
Iac setup
Power sharing level: limits the cur-
rent at the 230 V input (overload
protection).
Power
Determines the power sharing mode:
Sharing
Disable = deactivated
GEN. = generator function
SUPP. = support function
SHAR. = power sharing
"SHAR." enables the power sharing
function.
"SHAR. GEN." enables the power
sharing and generator functions.
"SHAR. SUPP." enables the power
sharing and support functions.
"SHAR. SUPP. GEN." enables the
power sharing, support and genera-
tor functions.
EN
Configuring the device with the remote control
Explanation
The device acts as a charger and, if necessary, as an
inverter if there is not sufficient current at the AC input.
The device only acts as a charger. The inverter function is
deactivated.
Value range
Default
3 A – 25 A
3 A
Disable
Disable
SHAR.
SHAR. GEN.
SHAR. SUPP.
SHAR. SUPP. GEN.
49