8. Troubleshooting procedure
If the Classic does not deliver voltage
•
Check mains presence on the mains terminal strip
•
Check the fuses
•
Check the voltage on the load terminal
•
The voltage on the battery cables must be identical to that of the load
•
Check that each 12 Vdc battery has a voltage greater than or equal to 11.5 Vdc
•
Repeat the measurement after having disconnected the load and the battery
•
If all the steps are validated, check the compatibility of your load
If the battery does not take over after a mains fault
•
Check the voltage on the battery terminals
•
Check the battery fuse
•
Check the voltage on terminal load1
If the indicator lights are not illuminated
•
Check mains presence on the mains terminal strip
•
Check the battery connection (and the battery fuse)
•
Check the voltage on terminal load
For additional technical assistance, contact the SLAT hotline
For return requests, visit our website
http://www.slat.fr/formulaireRMA.php
or contact SLAT After-Sales Service to obtain an RMA (Return Material Authorisation)
number).
Returns are not accepted without an RMA number.