1. General information
1.1. Correspondence table
12 V
24 V
48 V
The currents (In) shown are at rated output power.
1.2. Environmental specifications
Operating temperature:
-5 °C to +40 °C at 100 % of charge, for 150 W.
-5 °C to +50 °C at 75 % of charge, for 150 W.
-5 °C to +50 °C at 100 % of charge from 75 W to 100 W.
Storage temperature: -25 to +85 °C.
Relative humidity: 20 to 95 %.
1.3. Electrical input and output specifications
1.3.1 Network input
-
single-phase voltage: 98 V to 264 V except 100-150 W: 195 V to 264 V.
frequency: 47 to 63 Hz.
-
class I.
-
neutral systems: TT, TN, IT.
-
Primary current @ 98 V
Primary current @ 195 V
Circuit breaker to be provided upstream: D curve
1.3.2 Output
Rated voltage
Floating voltage set at half-load and at 25 °C
Adjustment range (V) *
Limitation current
* In power supply mode without battery exclusively. All use of the adjustment range in charger mode
with the battery will void the product's warranty.
75 W
100 W
6 A
8 A
3 A
4 A
1.5 A
2 A
75 W
1 A
0.5 A
13.6 V
24
150 W
12 A
6 A
3 A
100 W
-
0.75 A
12 V
24 V
27.2 V
±0.5 %
12-14 V
23-29 V
In
150 W
-
1 A
48 V
54.4 V
±0.5 %
±0.5 %
46-58 V