ELECTRODE - DEFLECTOR SETTING
After having installed the nozzle, check the correct position of the electrodes and deflector according to the
following measurements in mm.
It is advisable to check the measurements after every intervention on the head.
PUMP PRESSURE ADJUSTEMENT
The pump pressure is factory pre-set to 12 bar. To check the pressure use an oil-bathed pressure manometer.
Pressure can be regulated to between 11 and 14 bar for FIRE 1, FIRE 3, FIRE 6, FIRE 9 burners and between 7
and 14 bar for FIRE 1R, FIRE 3R, FIRE 6R burners.
SUNTEC - AS 47
m H
O
2
¸
3
4
¸
2
3
DANFOSS - BFP 11
Prex. bar
+
_
m H
O
2
Prex. bar
+
_
m H
O
2
¸
3,5
4
¸
6,5
7
DELTA- VM 1
Prex. bar
+
_
1009DIS726