Positioning

During positioning consider these elements:
Technical spaces requested by the unit
Electrical connections
Water connections
Spaces for air exhaust and intake
3.1 Functional spaces
Functional spaces are designed to:
guarantee good unit operation
carry out maintenance operations
protect authorized operators and exposed people
Respect all functional spaces indicated in the DIMENSIONS section.
Double all functional spaces if two or more unit are aligned.
3.2 Positioning
Units are designed to be installed:
EXTERNAL
in fixed positions
Limit vibration transmission:
use antivibration devices on unit bearing points
Choose the installation place according to the following criteria:
Customer approval
safe accessible position
technical spaces requested by the unit
spaces for the air intake/exhaust
Standard unit operating range at full load
verify unit weight and bearing point capacity
verify that all bearing points are aligned and leveled
install the unit raised from the ground
max. distance allowed by the electrical connections
Prefer places where the unit doesn't disturb the neighbours.
Avoid installations next to bedrooms or windows.
Avoid snow accumulations on batteries.
A correct circulation of the air is mandatory to guarantee the good unit operating.
Avoid therefore:
obstacles to the airflow
difficulty of exchange
leaves or other foreign bodies that can obstruct the air coil
winds that hinder or favour the airflow
heat or pollution sources close to the unit (chimneys, extractors etc..)
stratification (cold air that stagnates at the bottom)
recirculation (expelled air that is sucked in again)
incorrect positioning, close to very high walls, attics or in angles that could give rise to stratification or recirculation phenomenons
Ignoring the previous indications could:
reduce energy efficiency
alarm lockout due to HIGH PRESSURE (in summer) or LOW PRESSURE (in winter)
3.3 Saftey valve gas side
The installer is responsible for evaluating the opportunity of installing drain tubes, in conformity with the local regulations in force (EN 378).