Temporary Lighting

You do not need to install a temporary distribution
panel. Connect load wires into the appropriate
terminal blocks. Each input breaker can supply
power to a load while the bypass jumper protects
the module from load faults.
Warning! Verify that the panel is fed from
the correct voltage. A feed miswire or loss
of a feed neutral can cause over-voltage
damage to the equipment. Do NOT
remove bypass jumpers at this point--they
protect the modules from load faults.
14 Installation Guide for Dimming Panels
Input
circuit
breaker
Bypass jumper
protects the
module from load
faults.
N N o o t t e e : :
230 V
(CE) and
220-240 V
(non-CE) terminals
are marked:
• L for Live
• SL for Switched
Live