Precautions for outdoor unit combinations
Refer to [Fig. 9.2.2] for the positioning of twinning pipes.
[Fig. 9.2.2]
<A> Make sure the pipes from the twinning pipe to the outdoor unit are sloped downwards (high-pressure side only).
A
D
<B> Slope of twinning pipes (high-pressure side only)
Make sure the slope of the twinning pipes are at an angle within ±15° to the ground.
If the slope exceeds the specifi ed angle, the unit may be damaged.
E
A
Downward slope
C
BC controller
E
Slope of the twinning pipe is at an angle within ±15° to the ground
Caution:
•
Do not install traps to prevent oil backfl ow and compressor start-up failure.
•
Do not install solenoid valves to prevent oil backfl ow and compressor start-up failure.
•
Do not install a sight glass because it may show improper refrigerant fl ow.
If a sight glass is installed, inexperienced technicians that use the glass may overcharge the refrigerant.