Technical Data - CEAG COOPER Crouse-Hinds GHG 981 Mode D'emploi

Distributions de prises de maintenance et de réparation
Table des Matières

Publicité

Les langues disponibles

Les langues disponibles

Attention:
The safety switch of the maintenance and
repair supply socket distribution shall be
safeguarded against unauthorized use by
means of a padlock (padlock shackle Ø =
4-6 mm, see page 10, Fig. 1).
The cover cannot be removed when the
safety switch is in the OFF position.
Operation of supply socket distributions is
only permitted if a "Hot Work Permit"
has been granted.
Before switching on, ensure that there is no
potentially explosive gas atmosphere.
Dimensions in mm
X = Fixing dimensions
Maintenance and repair supply socket
distributions, GHG 981 0042 / 40A
8 8 8 8 8
Cooper Crouse-Hinds GmbH
Maintenance and repair supply socket distributions, GHG 981

Technical data

1
1.1
Supply socket distributions GHG 981 - 40A
Marking acc. to 94/9/EC and directive:
EC-type examination certificate:
Rated voltage:
Rated current:
Back-up fuse:
Switching capacity AC 3:
Perm. ambient temperature:
other temperatures possible for special versions.
Perm. storage temperature in original packing:
Protection category acc. to EN/IEC 60529
with closed and secured hinged cover, as well
as correctly inserted CEAG plugs:
Insulation class acc. to EN/IEC 61140:
Cable entry (standard version):
Supply terminal:
Test torques:
Cap nut of the plastic cable entry
for min. cable Ø in Nm
for max. cable Ø in Nm
Cover screws
Terminals
Weight (standard version):
II 2 G Ex e d II C T6
PTB 00 ATEX 1100X
bis 420V, 50/60 Hz
max. 40A
max. 80A gL
420V / 40A
-20° C to +40° C (standard version)
-40° C to +80° C
IP 66 (standard version)
I - is complied with by the devices
1xM40 (Ø 16-28mm)+1xM25 (Ø 8-17mm)
2 x 4 - 16mm²
M25
M40
5,00
11,0
3,50
5,00
2.5 Nm
2.5 Nm
ca. 8.90 kg
Wiring diagram
GHG 981 0042 / 40A

Publicité

Table des Matières
loading

Table des Matières