MEMORISING ONE OR MORE RADIO CONTROLS
Stagnoli control units can memorise 76 transmitters per channel in both rollingcode and fixed code. They are set by default to memorise Stagnoli
Rollingcode transmitters. To memorise fixed codes, modify "CF" parameters in the "FUNCTIONS" menu.
In addition, Stagnoli control units provide two memory channels:
1- the first channel controls automation: open-stop-close (or as programmed)
2- the second is used for pedestrian opening
-
R 00
AGG
-
DESCRIPTION OF PARAMETERS
(automatic closing time)= This is the time from when the gate is fully open to when it is closed,
TCA
which is automatic if CA=1. If the photocell is engaged, count time is reset.
(pedestrian opening)= This is the length of the pedestrian stroke (partial opening of leaf 1) ex-
TPED
pressed in % in reference to the total stroke.
(delay in opening time)= Delay time in seconds for leaf 2 opening.
SFAP
(delay in closing time)= Delay time in seconds of leaf 1 closing.
SFCH
(slowing space)= Space where stroke slows down both in opening and in closing,
rall
Equals: 1x10cm.
(anti-crushing force of leaf in opening)= This is the anti-crushing force of the leaf of the gate
FAP
stated in % compared with the maximum force in the opening phase. **
(anti-crushing force of leaf in closing)= This is the anti-crushing force of the leaf of the gate stat-
FCH
ed in % compared with the maximum force in the closing phase. **
(movement speed)= Movement speed\ (this parameter also automatically modifies slowing
VEL
speed).
(strike space)= This is the space, expressed in cm, at the tip of the leaf before the stop in open-
sba
ing and closing in which the control unit interprets obstacles as limit stops.
(relax time)= When the motor arrives at limit stop, both in opening and in closing, the direction of
Trel
travel is reversed for the set time, relaxing mechanical components
Equals: 1x10ms
(electric lock time)= This is the electric lock power supply time.
tAUX
** Stagnoli control units automatically memorise the forces necessary (FCH and FAP) for gate leaf movement, adding 10% to the average forces
detected during self-learning. Stagnoli delegates the correct setting of anti-crushing forces (FCH and FAP) in accordance with standard EN
12445 to installers.
PREM
1 ch
Press the
ok
transmitter button.
Default: 10sec
Min: 1sec
Max: 240sec
Default: 50%
Min: 30%
Max: 99%
Default: 1 sec
Min: 0 sec
Max: 10 sec
Default: 3 sec
Min: 0 sec
Max: 10 sec
Default: 2
Min: 1
Max: 10
Default: 50
Min: 20
Max: 99
Default: 50
Min: 20
Max: 99
Default: 5
Min: 1
Max: 10
Default: 4
Min: 1
Max: cm
Default: 2
Min: 0
Max: 20
Default: 1 sec
Min: 0 sec
Max: 2 sec
13