5.4
Use in flood hazard areas
6
Maintenance
7
Troubleshooting
Problem
Heavy oil foam in
the float chamber
due to excessive
amounts of air
sucked in (in excess
of the possible sep-
aration capacity of
4 l/h).
FloCo-Top-1K
FloCo-Top-1K is suitable for flood hazard areas. FloCo-Top-1K is
watertight up to 10 m water column (1 bar pressure).
After a flood, FloCo-Top-1K must be replaced.
Check FloCo-Top 1K for proper function.
Table 5: Maintenance times
When
If required
Annually or if
required
Every 5 years
No later than
after 20 years
Repairs may only be performed by specially trained, qualified staff.
Table 6: Troubleshooting
Possible reason
Leak in the suction line
Screw connections at the
suction side not tight
Initial commissioning with-
out separate suction pump
Suction line rating too great
– English –
Activity
Clean the plastic parts with soap suds, do
not use cleaning agents containing sol-
vents.
Replacing the filter insert
Replacing the burner hoses
Replace product
Repair
Perform a tightness test of
the suction line (vacuum test
or pressure test).
Seal the screw connections
Use suction pump
Observe DIN 4755-2: Flow
rate 0.2-0.5 m/s
Maintenance
25