CORTINA – CORTINA Forno
H min.
CHIMNEY CAPS - DISTANCES AND POSITIONING
Inclination of the
roof
α α α α
15°
30°
45°
60°
6.

CONNECTION TO THE CHIMNEY

For safety reasons the door of the appliances with constructive system 1, must be opened only for the
loading of the fuel or for removing the ashes, while during the operation and the rest, the door of the hearth
must remain closed.
The appliances with constructive system 2 must be connected to their own flue. The operating with open
door is allowed under supervision.
The stove is endowed with an upper exhaust pipe. The connection pipe to the flue must be the shortest
possible, right, tight and according to the current regulations.
The connection to the chimney must be performed with stable and strong pipes (we recommend a
thickness of 2 mm). The pipe for smokes exhaust must be fixed hermetically to the chimney. The diameter
7196100 Rev.08 – EN
> _ A
>A
(1)Ridge axis
α
Picture 7
Distance between the roof
ridge and the stack
A (m)
< 1.85 m
> 1.85 m
< 1.50 m
> 1.50 m
< 1.30 m
> 1.30 m
< 1.20 m
> 1.20 m
0,5 m
(2)Roof
UNI 10683/98
Minimum height of the stack
(measured from the outlet)
H (m)
0.50 m
above the roof ridge
1.00 m
from the roof
0.50 m
above the roof ridge
1.30 m
from the roof
0.50 m
above the roof ridge
2.00 m
from the roof
0.50 m
above the roof ridge
2.60 m
from the roof
23