Should it be necessary to exceed the ridge of the roof, the chimney cap must assure the discharge also in
case of windy weather (Picture 4).
(1) Industrial chimney cap
with
elements – it allows an
excellent discharge of the
smokes.
The chimney cap must meet the following requirements:
have internal section equivalent to that of the stack.
have a useful output section twice as big as the flue internal one.
be manufactured in such a way as to prevent the penetration of rain, snow, and any other foreign
body in the flue.
be easily checkable, for any possible maintenance and cleaning operation.
50 cm
2 m
1
m
22
pre- fabricated
10 m
(2) Handicraft chimney cap.
The right output section must
be at least twice as big as the
internal section of the flue
(ideal value: 2.5 times).
(1) In case of flues side by side, a chimney cap must be higher
than the other one of at least 50 cm in order to avoid pressure
transfers between the flues themselves.
(1) The chimney cap must not show hindrances within 10 m from
walls, pitches and trees. Otherwise raise it of at least 1 m over the
hindrance.
The chimney cap must exceed the ridge of the roof of at least 1 m.
CORTINA – CORTINA Forno
(3) Chimney cap for steel
flue with internal cone
deflector of smokes.
Picture 4
Picture 5
Picture 6
7196100 Rev.08 – EN