Installation; Preparation; Equipment Inspection; Necessary Equipment And Tools - Tripp-Lite SUT40KMBP Manuel D'installation Et D'utilisation

Panneau de dérivation d'entretien
Table des Matières

Publicité

Les langues disponibles

Les langues disponibles

7. Installation

7.1 Preparation

7.1.1 Equipment Inspection

Remove the equipment from the packaging material and inspect for any shipping damage that may have been overlooked upon receipt of
goods. Verify that the system includes all necessary hardware for installation.

7.1.2 Necessary Equipment and Tools

• Properly insulated tools
• Properly sized and rated mounting hardware

7.1.3 Installation Safety Precautions

Before proceeding with system installation, be sure to review and understand all of the SAFETY PRECAUTIONS in this manual!
AC VOLTAGE WARNING
The input/output voltage in this equipment can be up to 240 VAC. Be sure to fully read and understand this manual and verify that all
AC connections are correct and properly torqued. Use extreme caution when installing and maintaining the system!

7.1.4 Storage

If the equipment cannot be immediately installed, it should be stored in a clean and dry indoor location with adequate air circulation and
uniform temperature to prevent condensation. If the equipment must be stored for any length of time, it should be covered to protect it from
dust, debris and moisture.

7.2 Installation Steps

Before installing or maintaining this system, it is extremely important to read this manual and be sure that all system drawings and
schematics are reviewed and clearly understood. If there are any questions concerning this manual or any of the installation or
maintenance procedures and/or requirements, please contact a Tripp Lite representative before proceeding.

7.2.1 Equipment Location

This equipment is intended to be installed in a restricted access location.
The permanent location of the equipment must be on a smooth and solid wall surface. Do not locate the equipment against a non-fireproof
ceiling. Allow a space of 3 feet between the ceiling and the equipment unless an adequate fireproof shield is provided. Also verify that the
selected location will provide working clearances in compliance with article 110.26 of the National Electrical Code (NEC). Environmental
conditions of the selected location should also be reviewed. Refer to section 6.2 Environmental for environmental specifications.

7.2.2 Equipment Mounting

The equipment should be reliably secured to the mounting surface. Do not depend on wooden plugs driven into holes in masonry, concrete,
plaster or similar materials in accordance with Article 110.13 of the National Electrical Code (NEC). Secure the equipment utilizing the four
0.34-inch diameter mounting holes located in the back of the equipment. A set of equipment drawings for the specific configuration of
the equipment is included inside the equipment. Reference the equipment drawings or mounting hole size and locations. (See drawings in
Reference Materials section.)

7.2.3 Equipment Connections

Never work on power equipment while it is energized. De-energize equipment and lock off all power to the equipment before working
inside.
The top and bottom panel of the equipment is the recommended designated area for landing conduit to the equipment. All conduits must
be located to avoid interference with structural members and live bus. A set of drawings for the specific configuration of the equipment is
included inside the equipment. Reference the equipment drawings to locate the designated cable entry areas of the equipment.
All conductors are to be sized for 167°F (75°C) ampacity. When cable is used with temperature ratings above 167°F/75°C, it shall be
sized based on the ampacity of cable rated 167°F (75°C).
The equipment must be grounded with the appropriately sized conductor in compliance with Article 250 of the National Electrical
Code (NEC). The ground conductor should be terminated to the main ground bus bar inside the equipment.
Remove the equipment covers as needed to access the input and output connection points. Where cables enter or exit the equipment or
pass through any metal which has magnetic properties, they shall be arranged so all phase and neutral conductors are grouped together
and pass through the same opening in compliance with Article 300.20 of the National Electrical Code (NEC). When pulling cable into the
equipment, take care not to damage any of the internal components and control wiring. Position the cables inside of the equipment so they
are not subject to physical damage and are not forced permanently against the edges of any metal parts. If any cables are in contact with
sharp edges, place suitable protective material between the cable and the metal edge to protect the cable insulation.
4

Publicité

Table des Matières
loading

Ce manuel est également adapté pour:

Sut60kmbp

Table des Matières