MODEL
L ( m )
AEI1G30
EG
Supply power wire A:
Multipolar electric wire. Size and length of the suggested electric wire are showed on table "electrical data". The wire
must be Mod. H07RN-F (according to CEI 20-19 CENELEC HD 22). Make sure the length of the conductors between
the fixing point and the terminals allows the straining of the conductors L, N before that of the grounding.
Connecting wire B (SHIELDED):
Bipolar electric shielded wire; size and length of the suggested electric wire are showed on table "electrical data".
The wires have not to be lighter than Mod. H05VVC4V5-K (according to CEI 20-20 CENELEC HD21).
Connecting wire C (with ground conductor):
Multipolar electric wire; size and length of the suggested electric wire are showed on table "electrical data". The
wires have not to be lighter than Mod. H07RN-F (according to CEI 20-19 CENELEC HD22).
ADDITIONAL MATERIAL REQUIRED FOR INSTALLATION (NOT SUPPLIED)
●
Deoxidized annealed copper tube for refrigerant tubing connecting the units of the system; it has to be insulated with foamed polyethylene
(min. thickness 8mm).
NARROW TUBE
OUTER DIAMETER
6,35 mm
●
PVC pipe for condensate drain pipe (ø int.18mm) in length suitable to let the condensate flow into the outside drainage.
●
Anti-freeze oil for flare connections (about 30g.).
●
Electric wire: use insulated copper wires of size and length as shown at paragraph "SYSTEM WIRING DIAGRAMS".
TUBING LENGTH AND ELEVATION DIFFERENCE LIMITS
TOTAL TUBING LENGHT
AT SHIPMENT (m)
REQUIRED AMOUNT OF ADDITIONAL REFRIGERANT
For tubing 1/4 " - 3/8" = 15g/m
For tubing 1/4 " - 1/2" = 20g/m
For tubing Emix (3/8") = 15g/m
LIMIT OF ELEVATION DIFFERENCE - OUTDOOR UNIT/INDOOR UNIT: 10m (H)
No additional charge of compressor oil is necessary.
LENGTH, SIZE WIRES AND DELAYED FUSE
A
2
S ( mm
)
L ( m )
15
1,5
MIN. THICKNESS
0,8 mm
H
7,5
B
2
S ( mm
)
L ( m )
15
0,75
OUTER DIAMETER
9,52 mm
TOTAL TUBING LENGHT
WITH ADDITIONAL REFRIGERANT (m)
15
4
C
2
S ( mm
)
15
1,5
LARGE TUBE
MIN. THICKNESS
0,8 mm
H
10 A