The Wattstopper CI-355 360° passive infrared (PIR) occupancy sensors turn lighting systems on and off based on occupancy and
ambient light levels. The light level feature can be used to keep lights from turning on if the ambient light level is sufficient.
The sensors can be configured to turn lighting on, and hold it on as long as the sensor detects occupancy. After no movement is
detected for a user specified time (30 seconds to 30 minutes) the lights are switched off. A "walk-through" mode can turn lights off after
only 3 minutes, if no activity is detected after 30 seconds of an occupancy detection.
The CI-355 operates on 120VAC, 230VAC (1Ø), 277VAC, or 347VAC.
The CI-355 provides a 360° coverage pattern. Two lens patterns are available. The CI-355 provides up to 1200 square feet of coverage
and the CI-355-1 provides up to 500 square feet of coverage. The coverage shown represents walking motion at a mounting height of
8 feet. For building spaces with lower levels of activity or with obstacles and barriers, coverage size may decrease.
CI-355 Coverage Pattern (standard lens)
Side View
0
8' (2.4m)
10' (3m)
12' (3.7m)
40'
(12.2m)
(9.1m)
CI-355-1 Coverage Pattern (high density, reduced range lens)
Side View
0
8' (2.4m)
10' (3m)
12' (3.7m)
20'
15'
(6.1m)
(4.6m)
DESCRIPTION AND OPERATION
30'
20'
10'
0
(6.1m)
(3m)
10'
5'
0
(3m)
(1.5m)
(1.5m)
Wattstopper
360° Passive Infrared Line Voltage Occupancy Sensor (version 3)
with Light Level Feature
Détecteur de présence de tension de ligne infra-rouge passif à 360° (v3)
avec fonction niveau de luminosité
Sensor de ocupación infrarrojo pasivo de 360° voltaje de línea (v3)
con función de nivel de luz
Installation Instructions • Instructions d'Installation • Instrucciones de Instalación
Voltages ......................................................120//230/277/347VAC, 50/60Hz
Load Ratings
@120VAC ........................................0-800W Ballast/Tungsten/LED
@230VAC (Single Phase)...............................0-1200W Ballast/LED
@277VAC .....................................................0-1200W Ballast/LED
@347VAC ......................................................0-1500W Ballast/LED
Operating Temperature ........................................ 32° to 131°F (0° to 55°C)
Light Level One-Step Adjustment ............................................10FC–300FC
Time Delay Adjustment ....................................... 30 seconds to 30 minutes
Walk-Through Mode ................. 3 minutes if no activity after 30 sec.
Test Mode ............................................5 sec. upon DIP switch reset
PIR Coverage
Model CI-355 ................................................................ up to 1200ft
Model CI-355-1 .............................................................. up to 500ft
Sensitivity Adjustment ...............................High or Low (DIP switch)
COVERAGE PATTERN
10'
20'
30'
40'
(3m)
(6.1m)
(9.1m)
(12.2m)
5'
10'
15'
20'
(3m)
(4.6m)
(6.1m)
®
SPECIFICATIONS
Top View @ 8ft
Top View @ 8ft
2
2
24 ft
7.3m