No: 24658 – 11/17 rev. 1
Catalog Number • Numéro de Catalogue • Número de Catálogo: LMIO-102
Country of Origin: Made in China • Pays d'origine: Fabriqué en Chine • País de origen: Hecho en China
This unit is pre-set for Plug n' Go™ operation,
adjustment is optional.
For full operational details, adjustment and more features
of the product, see the DLM System Installation Guide
provided with Wattstopper room controllers, and also
available at www.legrand.us/wattstopper.
Installation shall be in accordance with all applicable
regulations, local and NEC codes. Wire connections shall
be rated suitable for the wire size (lead and building wiring)
employed.
For Class 2 DLM devices and device wiring: To be
connected to a Class 2 power source only. Do not reclassify
and install as Class 1, or Power and Lighting Wiring.
The Lighting Management LMIO-102 device automatically coordinates lighting for up to four moveable walls. It has four inputs for four
moveable walls equipped with (third party) contact closures.
MOUNTING AND WIRING
Installation shall be in accordance with all applicable regulations, wiring practices,
and codes. Connect to a Class 2 power source only.
• Class 2 Device Wiring Only – Do Not Reclassify and Install as Class 1, 3, or
Power and Lighting Wiring.
• Wire connections shall be rated suitable for the wire size (lead and building
wiring) employed.
The LMIO-102 is UL2043 Plenum rated.
All connections to the LMIO-102 are Class 2 low voltage.
If code requires that the LMIO-102 be mounted in an enclosure, it can be
mounted inside a 4" x 4" junction box, inside a 21/8" deep (or deeper) 2-gang wall
box, in a 3" or 4" octagonal box, or on a DIN rail inside a panel.
Attach DIN rail
Option 1: Attach
clip
to DIN rail
The DLM local network uses free topology low voltage wiring. The LMIO-102 can connect anywhere on the DLM local network.
Wattstopper
DLM Partition Interface
DLM Interface de partition
DLM Interfaz de la partición
Installation Instructions • Instructions d'Installation • Instrucciones de Instalación
DESCRIPTION
Option 2: Mount
Inside a 2-gang
to wall
J-box
ATTACH THE LMRJ CABLE
®
SPECIFICATIONS
Voltage ....................................................................24VDC
Current Consumption ................................................ 20mA
Power Supply .......................Wattstopper Room Controller
Connection to the DLM Local Network ..........2 RJ-45 ports
Environment ....................................... For Indoor Use Only
Operating Temperature ...... 32° to 104°F (0° to 40°C)
Storage Temperature ........ 23° to 176°F (-5° to 80°C)
Relative Humidity ............ 5 to 95% (non condensing)
RoHS compliant, UL2043 Plenum rated
Patent Pending
Connect to
Blue LEDs = Wall Closed
DLM local network
Wall 1
NOT Ethernet
Wall 2
Wall 3
Wall 4
Not Used
+24VDC
CAUTION: LMSW-108 DOES
NOT WORK WITH PARTITIONING.
Wall 1
Wall 2
Wall 3
Wall 4
Wall 4
Wall 3
Wall 2
Wall 1