6
Electrical installation
Wiring
6.4
Wiring
(
Stop!
ƒ
ƒ
How to wire the filter:
1. Connect the connection cables "load" 0 to the basic device.
– Observe the Mounting Instructions for the basic device!
2. Wire the terminals of the thermostat 1.
– Observe tightening torque!
– Switching capacity: 250 V AC / 1.6 A (NC contact)
– Integrate the thermal contact into the monitoring system so that the mains supply
is switched off when the filter is overheated.
3. Attach the PE conductor to the PE stud 2 with the ring cable lug.
– Observe tightening torque!
4. Connect the mains cables to the screw terminal "line" 2.
– Observe tightening torque!
38
Observe the Mounting Instructions for the basic device when wiring the
mains filter.
Ensure permanent electrical connections.
0
1
2
3
0
Connection cables "load"
1
Screw terminals "thermostat"
2
PE stud
3
Screw terminals "line"
l
8200vec106
EDK82ZN903 DE/EN/FR 5.1