Fault
Insufficient water
Crossflow, hot water being forced
into cold water pipe, or vice versa,
when mixer is closed
Spout temperature does not cor-
respond with temperature set
Temperature regulation not possible
Shower or spout dripping
Instantaneous heater didn't work with
thermostat
English
Cause
- Supply pressure inadequate
- Regulator filter dirty
- Shower filter seal dirty
- Backflow preventers dirty or leaking - Clean backflow preventers, ex-
- Thermostat has not been adjusted
- Hot water temperature too low
- thermo cartridge calcified
- Dirt or sedimentation on valve seat,
shut-off unit damaged
- Filters are dirty
- check valve hasn't moved back
- Flow limiter in handshower isn't
removed
Assembly
see
page
8
Spare
parts
(see page 15)
Cleaning
(see page 16)
Test
certificate
(see page 16)
Remedy
- Check water pressure (If a pump
has been installed check to see if
the pump is working).
- Clean filter in front of the mixer and
on the MTC-thermo cartridge
- Clean filter seal between shower
and hose
change if necessary
- Adjust thermostat
- Increase hot water temperature to
42 ºC to 65 ºC
- Exchange thermo cartridge
- Clean or exchange shut-off unit
- Clean the filter / exchange filter
- Exchange check valves
- Remove flow limiter
7