Télécharger Imprimer la page

ENAG CDS3 12V/80A Manuel D'utilisation page 45

Publicité

Les langues disponibles
  • FR

Les langues disponibles

  • FRANÇAIS, page 1
These options must be connected to K10 with a specific cable, ref. DEP-V-A-CDS3 (for further information,
please contact ENAG).
Remote LEDs accessory : reference LED-DEP-CDS3
Allows having at distance the charger LED: ON/BOOST, absorption/Floating.
A 5-metre cable to connect on KLD123.
Plastic cable glands : reference PE-CDS3/3M
To be mounted in place of the cable bushings of origin.
Packet including 4 plastic cable glands.
Power-sharing function (K19 connector)
Allows to balance the voltage and current regulation, when chargers are mounted into parallel (up to 6
chargers : 1 master + 5 slaves).
This function can be done by connecting a specific cable (can be ordered on option) on K19 connector of the
parallel-mounted chargers.
This function can only operate if :
• The chargers have the same size (voltage and current)
• The chargers have the same settings (RC1 and SW1)
Mounting of 2 chargers into parallel :
3 output charger
(in case of charger setting)
- BAT
AC input
L7 /
Same length and cable section
for links L1 to L8.
+ BAT D
+ BAT 1
+ BAT 2
L1 /
L2 /
L3 /
Power Sharing Link (K19)
CDS3-3M-DEE
3 output charger
(in case of charger setting)
- BAT
AC input
L4 /
L8 /
20-07-09 N°10350 22A
+ BAT D
+ BAT 1 + BAT 2
L5 /
L6 /
43

Publicité

loading

Ce manuel est également adapté pour:

Cds3 24v/60aCds3 48v/30aCds3 24v/75a