Control Cable Specifications - Mitsubishi Electric City Multi PURY-P72TLMU-A Manuel D'installation

Table des Matières

Publicité

Les langues disponibles

Les langues disponibles

・Power cable size and device capacity
MOP is used to select the fuse, switch, or breaker for current leakage.
Outdoor unit model
Unit combination
PURY-P72TLMU-A(-BS)
PURY-P96TLMU-A(-BS)
PURY-P120TLMU-A(-BS)
PURY-P144TLMU-A(-BS)
PURY-P168TLMU-A(-BS)
PURY-P72TLMU-A(-BS)
PURY-P144TSLMU-A(-BS)
PURY-P72TLMU-A(-BS)
PURY-P96TLMU-A(-BS)
PURY-P168TSLMU-A(-BS)
PURY-P72TLMU-A(-BS)
PURY-P96TLMU-A(-BS)
PURY-P192TSLMU-A(-BS)
PURY-P96TLMU-A(-BS)
PURY-P120TLMU-A(-BS)
PURY-P216TSLMU-A(-BS)
PURY-P96TLMU-A(-BS)
PURY-P120TLMU-A(-BS)
PURY-P240TSLMU-A(-BS)
PURY-P120TLMU-A(-BS)
PURY-P144TLMU-A(-BS)
PURY-P264TSLMU-A(-BS)
PURY-P120TLMU-A(-BS)
PURY-P144TLMU-A(-BS)
PURY-P288TSLMU-A(-BS)
PURY-P144TLMU-A(-BS)
PURY-P144TLMU-A(-BS)
PURY-P312TSLMU-A(-BS)
PURY-P168TLMU-A(-BS)
PURY-P168TLMU-A(-BS)
PURY-P336TSLMU-A(-BS)
PURY-P168TLMU-A(-BS)
PURY-P72YLMU-A(-BS)
PURY-P96YLMU-A(-BS)
PURY-P120YLMU-A(-BS)
PURY-P144YLMU-A(-BS)
PURY-P168YLMU-A(-BS)
PURY-P72YLMU-A(-BS)
PURY-P144YSLMU-A(-BS)
PURY-P72YLMU-A(-BS)
PURY-P96YLMU-A(-BS)
PURY-P168YSLMU-A(-BS)
PURY-P72YLMU-A(-BS)
PURY-P96YLMU-A(-BS)
PURY-P192YSLMU-A(-BS)
PURY-P96YLMU-A(-BS)
PURY-P120YLMU-A(-BS)
PURY-P216YSLMU-A(-BS)
PURY-P96YLMU-A(-BS)
PURY-P120YLMU-A(-BS)
PURY-P240YSLMU-A(-BS)
PURY-P120YLMU-A(-BS)
PURY-P144YLMU-A(-BS)
PURY-P264YSLMU-A(-BS)
PURY-P120YLMU-A(-BS)
PURY-P144YLMU-A(-BS)
PURY-P288YSLMU-A(-BS)
PURY-P144YLMU-A(-BS)
PURY-P144YLMU-A(-BS)
PURY-P312YSLMU-A(-BS)
PURY-P168YLMU-A(-BS)
PURY-P168YLMU-A(-BS)
PURY-P336YSLMU-A(-BS)
PURY-P168YLMU-A(-BS)
・The wire size is the minimum value for metal conduit wiring. If the voltage drops, use a wire that is one size thicker in diameter. Make sure the
power-supply voltage does not drop more than 10%. Make sure that the voltage imbalance between the phases is 2% or less.
・Power supply cords of parts of appliances for outdoor use shall not be lighter than polychloroprene sheathed flexible cord (design 245 IEC57).
For example, use wiring such as YZW.

10-3. Control cable specifications

・Transmission cable
Type
2-core shielded cable CVVS, CPEVS, or MVVS
Size
1.25 mm
2
(AWG 16)
Length
Max. 200 m (656 ft)
The maximum allowable length of transmission cables via outdoor units (both centralized control transmission cables and indoor-outdoor transmission cables) is
Remarks
500 m (1640 ft).
The maximum allowable length of transmission cables from the power supply unit to each outdoor unit or to the system controller is 200 m (656 ft).
* Do not use a single multiple-core cable to connect indoor units that belong to different refrigerant systems. The use of a multiple-core cable may result in signal transmission errors and
malfunctions.
* Ensure shield continuity when extending the transmission cable.
・Remote controller cable
Type
Size
Max. 10 m (32 ft)
Length
* If the length exceeds 10 m (32 ft), use a 1.25 mm
cable.
WT07598X02
Minimum size [mm
2
(AWG)]
Power
Power cable after
cable
branching point
5.3 (10)
8.4 (8)
13.3 (6)
21.2 (4)
21.2 (4)
5.3 (10)
5.3 (10)
8.4 (8)
8.4 (8)
8.4 (8)
8.4 (8)
13.3 (6)
8.4 (8)
13.3 (6)
13.3 (6)
21.2 (4)
13.3 (6)
21.2 (4)
21.2 (4)
21.2 (4)
21.2 (4)
21.2 (4)
21.2 (4)
2.1 (14)
3.3 (12)
5.3 (10)
5.3 (10)
8.4 (8)
2.1 (14)
2.1 (14)
3.3 (12)
2.1 (14)
3.3 (12)
3.3 (12)
5.3 (10)
3.3 (12)
5.3 (10)
5.3 (10)
5.3 (10)
5.3 (10)
5.3 (10)
5.3 (10)
5.3 (10)
8.4 (8)
8.4 (8)
8.4 (8)
ME remote controller cable
2-core sheathed cable (unshielded) CVV
0.3–1.25 mm
2
(AWG 22–16) (0.75–1.25 mm
2
(AWG 16) shielded
Earth leakage breaker
Earth wire
5.3 (10)
30 A 30 mA or 100 mA 0.1 sec. or less
8.4 (8)
40 A 100 mA 0.1 sec. or less
13.3 (6)
50 A 100 mA 0.1 sec. or less
21.2 (4)
60 A 100 mA 0.1 sec. or less
21.2 (4)
70 A 100 mA 0.1 sec. or less
5.3 (10)
30 A 30 mA or 100 mA 0.1 sec. or less
5.3 (10)
30 A 30 mA or 100 mA 0.1 sec. or less
8.4 (8)
40 A 100 mA 0.1 sec. or less
8.4 (8)
30 A 30 mA or 100 mA 0.1 sec. or less
8.4 (8)
40 A 100 mA 0.1 sec. or less
8.4 (8)
40 A 100 mA 0.1 sec. or less
13.3 (6)
50 A 100 mA 0.1 sec. or less
8.4 (8)
40 A 100 mA 0.1 sec. or less
13.3 (6)
50 A 100 mA 0.1 sec. or less
13.3 (6)
50 A 100 mA 0.1 sec. or less
21.2 (4)
60 A 100 mA 0.1 sec. or less
13.3 (6)
50 A 100 mA 0.1 sec. or less
21.2 (4)
60 A 100 mA 0.1 sec. or less
21.2 (4)
60 A 100 mA 0.1 sec. or less
21.2 (4)
60 A 100 mA 0.1 sec. or less
21.2 (4)
70 A 100 mA 0.1 sec. or less
21.2 (4)
70 A 100 mA 0.1 sec. or less
21.2 (4)
70 A 100 mA 0.1 sec. or less
2.1 (14)
15 A 30 mA or 100 mA 0.1 sec. or less
3.3 (12)
20 A 30 mA or 100 mA 0.1 sec. or less
5.3 (10)
25 A 30 mA or 100 mA 0.1 sec. or less
5.3 (10)
30 A 30 mA or 100 mA 0.1 sec. or less
8.4 (8)
40 A 100 mA 0.1 sec. or less
2.1 (14)
15 A 30 mA or 100 mA 0.1 sec. or less
2.1 (14)
15 A 30 mA or 100 mA 0.1 sec. or less
3.3 (12)
20 A 30 mA or 100 mA 0.1 sec. or less
2.1 (14)
15 A 30 mA or 100 mA 0.1 sec. or less
3.3 (12)
20 A 30 mA or 100 mA 0.1 sec. or less
3.3 (12)
20 A 30 mA or 100 mA 0.1 sec. or less
5.3 (10)
25 A 30 mA or 100 mA 0.1 sec. or less
3.3 (12)
20 A 30 mA or 100 mA 0.1 sec. or less
5.3 (10)
25 A 30 mA or 100 mA 0.1 sec. or less
5.3 (10)
25 A 30 mA or 100 mA 0.1 sec. or less
5.3 (10)
30 A 30 mA or 100 mA 0.1 sec. or less
5.3 (10)
25 A 30 mA or 100 mA 0.1 sec. or less
5.3 (10)
30 A 30 mA or 100 mA 0.1 sec. or less
5.3 (10)
30 A 30 mA or 100 mA 0.1 sec. or less
5.3 (10)
30 A 30 mA or 100 mA 0.1 sec. or less
8.4 (8)
40 A 100 mA 0.1 sec. or less
8.4 (8)
40 A 100 mA 0.1 sec. or less
8.4 (8)
40 A 100 mA 0.1 sec. or less
MA remote controller cable
2
(AWG 18–16) if a simple remote controller is connected)
Max. 200 m (656 ft)
GB-30
Local switch
(A)
MCA (A)
MOP (A)
Capacity
30
24/22
35/35
40
33/30
50/50
50
42/39
60/60
60
52/48
80/70
70
68/63
110/100
30
24/22
35/35
30
24/22
35/35
40
33/30
50/50
30
24/22
35/35
40
33/30
50/50
40
33/30
50/50
50
42/39
60/60
40
33/30
50/50
50
42/39
60/60
50
42/39
60/60
60
52/48
80/70
50
42/39
60/60
60
52/48
80/70
60
52/48
80/70
60
68/63
110/100
70
52/48
80/70
70
68/63
110/100
70
68/63
110/100
15
11
20
20
15
25
25
19
30
30
24
35
40
31
50
15
11
20
15
11
20
20
15
25
15
11
20
20
15
25
20
15
25
25
19
30
20
15
25
25
19
30
25
19
30
30
24
35
25
19
30
30
24
35
30
24
35
30
31
50
40
24
35
40
31
50
40
31
50