CONNECTING THE INVERTER

Installation procedure:

1. Mount the inverter in a secure location. If the inverter is to be mounted on a
wall, mount it horizontally. Make sure that the front and rear of the inverter
has free air flow.
2. Make sure the cables are the proper gauge and have the fuse holder as
close to the battery bank's Positive (red) terminal.
3. Install the fuse in the Positive (red) cable.
4. Make sure the Power Switch located on the front panel of the inverter is in
the Off position.
5. Locate the ground lug terminal on the inverter. Connect an insulated 10
gauge copper wire to the terminal. The other end of the ground wire is
connected to a "proper" grounding point. Use the shortest practical length
of wire. Connect this wire to the chassis of your vehicle or to the grounding
system in your boat. In a city, the ground wire can connect to a metal cold
water pipe that goes underground. In remote locations, the ground wire
can be connected to an "earth ground". This can be an attachment to a foot
long copper clad metal rod driven into the ground. In the unlikely event of
a short circuit, operating the inverter without proper grounding can result in
electrical shock. Do not directly connect this ground wire to the Negative
(black) DC Terminal of the inverter. As an alternative grounding connection,
use the Negative (black) terminal of the battery.