12. Connections
Trimmer adjustment is strictly prohibited.
Signal Connector Information
Signal connector used (CN201)
Part Description
Pin Header
S8B-PHDSS(LF)(SN)
Matching Housings, Pin & Tool
Part Description
Socket Housing
Terminal Pins
YRS-620(SPHD-002T-P0.5)
Hand Crimping
 
Tool
YC-610R(SPHD-001T-P0.5)
Signal Connector Pin Assign
S8B-PHDSS(LF)(SN) (JST)
2
1
4
3
6
5
8
7
13. DRF240 series UL508 Listed Condition
WIRING
Connector
Recommended Wire
Input
10~24 AWG
(L, N,
)
Output
10~24 AWG
(+V, -V)
Output
10~24 AWG
(DC OK)
CN201
Part Name
Manufact.
JST
Part Name
Manufact.
PHDR-8VS
SPHD-002T-P0.5
SPHD-001T-P0.5
1.
CB
2.
CB_COM
3.
NC
4.
NC
5.
CNT+
6.
CNT-
7.
PV
8.
COM
Max. Torque
10.3 kgf.cm
(9 lbf.in)
10.3 kgf.cm
(9 lbf.in)
10.3 kgf.cm
(9 lbf.in)
1) Wire requirements, use minimum 75°C wire, use copper
conductor only.
2) For use in a Pollution degree 2 environment only.
3) These products are considered for use where maximum
surrounding air temperature does not exceed 70°C. When
installing these products please refer to section 9 for
derating.
4) Indoor use only.
14. DRF240 series ATEX/IEC Ex Conditions
(Model DRF240-24-1/HL-xyz only)
II3G Ex nA nC IIC T4 Gc
The DRF 240-24-1/HL is a sub model of the DRF240 series.
It has the same functionality as the standard DRF240 and
benefits from a conformal coating. It is suitable for
applications in Zone 2 provided it is installed in an
appropriate IP54 enclosure according EN60079-15. When
fitted in an IP54 enclosure, mounting method (section 8),
ambient temperature requirement and deratings (section 9)
JST
must be complied with. Do not adjust any trimmers when
JST
explosive atmosphere could be present.
JST
The DRF240-24-1/HL is approved to IEC/EN60079-0 and
IEC/EN60079-15 Protection type nA and nC.
The product is suitable for IIA, IIB and IIC gas atmospheres.
Temperature class T4 (maximum surface temp ≤ 135°C).
Product marking:
TDK-Lambda UK Ltd
Kingsley Avenue, Ilfracombe
Devon, EX34 8ES
Telephone - Sales and Service +44 (0)1271 856666
Head Office and Works +44 (0)1271 856600
Facsimile +44 (0)1271 864894
WEBSITE:
www.uk.tdk-lambda.com
TDK-Lambda
DRF240 Series
INSTRUCTION MANUAL

Publicité

Table des Matières
loading

Ce manuel est également adapté pour:

Drf240241

Table des Matières