PA619-04-01B
8. Mounting Directions
Recommended standard mounting method is vertical with the
output connector uppermost. Do not exceed the load deratings.
See section 9. Leave enough space surround the units to
ventilate heat efficiently.
40mm
or more
20mm
or more
A
Minimum Installation clearances:
40mm on top, 20mm on the bottom, A=5mm which is
recommended on the left and right side when products are
permanently loaded with full 240W. In case the adjacent
device is a heat source, A=15mm clearance is recommended.
Air Flow
A
Air Flow
8.1. Power supply mounting on DIN RAIL (TS35
or equivalent)
Make sure input and output wire disconnected when
mount power supply onto rail.
(1) Tilt the unit slightly rearwards, fit the unit
over top hat rail.
40mm
or more
20mm
or more
(2) Slide it downward until it hits the stop.
TDK-Lambda
DRF240 Series
INSTRUCTION MANUAL