Connection To Water System; Electric Controls; Control Panel - Zanotti SB Série Notice De Mode D'emploi Et D'entretien

Table des Matières

Publicité

Les langues disponibles
  • FR

Les langues disponibles

7.2 Connection to water system

This connection is only necessary if the unit has a water-cooled condenser. It is effected by following the
indications of the tags positioned by the INLET and OUTLET pipes. Connection pipes should never be
smaller in diameter than those on the unit. A minimum water pressure of 1 bar is required for correct
operation of the unit.
8.

ELECTRIC CONTROLS

8.1 Control panel

Control LED (GREEN)
ON: compressor is running, unit is refrigerating.
Flashing: compressor is in start delay mode.
OFF: compressor is off, room temperature is down to set value
Control LED (GREEN)
ON: evaporator fan is running.
Flashing: evaporator fan is in start delay mode. OFF:
evaporator fan is off. Defrost is in course.
Control LED (YELLOW)
ON: Automatic or manual defrost is in course.
Alarm LED (RED)
ON: alarm has been activated because of a malfunctioning sensor, or pressure switch
intervention, or cold room temperature exceeding allowed tolerances.
OFF : Unit is operating normally.
DISPLAY: on connection to the mains it shows OFF to indicate the condition of the unit. By
pressing ON/OFF key for 3 seconds the unit is turned ON and the display shows the cold room
temperature. In programming mode the parameters to be set are displayed; in alarm mode the
alarm code is displayed.
"SET" key: when pressed it lights up and allows room temperature to be set.
programming it is used to pass from a submenu to an
upper one..
"DOWN/ROOM LIGHT" key: in programming mode or when setting room temperature it is used
to reduce the value displayed; otherwise it is used to switch on/off the cold room light.
"SB.M./UP" key: in programming mode it is used to increase the values displayed. If pressed for
more than 5 seconds it enables manual defrost to be carried out.
"ON/OFF" key: when pressed for 3 seconds it turns the unit on or off.
"Enter" key: it gives access to programming menu and submenus. Access to the programming
mode requires the installator's assistance and should be effected only if necessary.
water condenser
(
)
During
27

Publicité

Table des Matières
loading

Ce manuel est également adapté pour:

Sb1Sb2Sb3Sb4Sb5

Table des Matières