11.The default value is 0,3 bar. This value of pressure is the one that the system
DIF. START
0,3 bar
will subtract to the input pressure, resulting the final pressure to which the
system will set in motion when the hydraulic network have a demand. Using
keys
between 0,3 and 0,6 bar. Example:
The value should be greater as much as smaller be the accumulation and vice
versa.
12. "TIMER STOP" default value is 5". This will be the employed time by the
TIMER STOP
5 s
system in stopping once ceased the consumption in all the installation. Using
keys
VIEW MODE
13. There are 2 view modes to choose::
PRESSURE
- Pressure: it is visualized "P LINE" (real pressure of the installation) and "SET P"
(working programmed pressure).
- Service: it is visualized "Hz" (working frequency of the inverter), "LINE" (input
pressure chosen), "SET P" (real pressure of the installation) y "FL" (flow sensor
state).
P LINE
SET P
14. After pressing ENTER pushbutton, the system will remain
0,0 bar
0,0 bar
configured showing the type of view chosen in the previous
Hz
LINE
SET P
FL
42
2,0 bar 2,0
1
section.
Press AUTOMATIC in order to quit manual mode.
REGISTER OF FUNCTIONS AND ALARMS
Pushing simultaneously MENU +
pushbutton ENTER we are able to advance inside the register, once we get the last register we can go back to the
main menu pushing ENTER again. The visualization sequence is as follows:
P LINE
SET P
0,0 bar
0,0
MENU+p
P LINE
SET P
0,0 bar
0,0
"CE" STAMENT OF COMPLIANCE.
COELBO CONTROL SYSTEM, S.L. We state, on our's own responsibility, thal all materials herewith related
comply with the following European standards:
2006/95/EC Low Voltage Directive on Electrical Safety
2004/108/CE Electromagnetic Compatibility.
2002/95/CE RoHS Directive
Product's name: SPEEDMATIC SET
Type: 2010 – 3010 – 2110 – 3110 – 21110 - 31110
As per the European Standards:
UNE EN 60730-1:1998+A11:1998+A2:1998+A14:1998+A15:1998+A16:1998+
A17:2001+ERRATUM A1:2001+A18:2003
UNE EN 60730-2-6:1997+A1:1998+A2:1999+CORR A1:2001+CORR A2:01
UNE EN 61000-6-2:2002
pq
to modify the initial value. It is recommended to maintain this value
- Input pressure:
- Differential start:
- Final start pressure:
pq
we can modify the initial.
p
during 3" we will get the register of functions and alarms, by mean of the
FUNCTION REGISTER
ENTER
HOURS
26 h
Register of operational controls
ALARM REGISTER
ENTER
NO WATER
Register of alarms
2
0,3 bar.
2 - 0,3 = 1,7 bar.
FUNCTION REGISTER
ENTER
STARTS
32
ALARM REGISTER
ENTER
I MAX. AUX.
0
bar.
AUTOMATIC
FUNCTION REGISTER
ENTER
CONNECTIONS
25
ALARM REGISTER
ENTER
TEMP.
0
Tehnical director
F. Roldán Cazorla
ENTER
ENTER
ENTER
ALARM REGISTER
SHORTCIRC.
0
ENTER
ALARM REGISTER
I MAX
0

Publicité

loading