Télécharger Imprimer la page

Publicité

Liens rapides

ZWD150PAF Installation Manual
ENGLISH
General Safety Instructions:
READ SAFETY INSTRUCTIONS
Servicing:
These products are not customer serviceable TDK-Lambda UK LTD and their authorised agents only are permitted
to carry out repairs.
Critical Components:
These products are not authorised for use as critical components in nuclear control systems, life support systems or
equipment for use in hazardous environments without the express written approval of the Managing Director of TDK-
Lambda EMEA.
Product Usage:
These products are designed for use within a host equipment which restricts access to authorised competent
personnel.
This product is a component power supply and is only to be installed by qualified persons within other equipment and
must be not operated as a stand alone product.
This product is for sale to business to business customers and can be obtained via distribution channels.
It is not intended for sale to end users.
This product is a component power supply and does not fall within the scope of the EMC directive. Compliance with
the EMC directive must be considered in the final installation. Please contact your local TDK-Lambda office.
Environmental:
These products are IPX0, and therefore chemicals/solvents, cleaning agents and other liquids must not be used.
Environment:
This power supply is a switch mode power supply for use in applications within a Pollution Degree 2, overvoltage
category II environment. Material Group IIIb PCB's are used within it.
Output Loading:
The output power taken from the power supply must not exceed the rating stated on the power supply label, except
as stated in the product limitations in this handbook.
Input Parameters:
This product must be operated within the input parameters stated in the product limitations in this handbook.
End of Life Disposal:
The unit contains components that require special disposal. Make sure that the unit is properly disposed of at the
end of its service life and in accordance with local regulations.
RISK OF ELECTRIC SHOCK
High Voltage Warning:
Dangerous voltages are present within the power supply. The professional installer must protect service personnel
from inadvertent contact with these dangerous voltages in the end equipment.
WARNING: When installed in a Class 1 end equipment, this product must be reliably earthed and professionally
installed.
The (+) or (-) output(s) can be earthed or left floating.
The unit cover(s)/chassis (where applicable) must not be made user accessible.
The mains input connector is not acceptable for use as field wiring terminals.
Page 1 of 12
PA573-04-01D (a)

Publicité

loading

Sommaire des Matières pour TDK-Lambda ZWD150PAF

  • Page 1 General Safety Instructions: READ SAFETY INSTRUCTIONS Servicing: These products are not customer serviceable TDK-Lambda UK LTD and their authorised agents only are permitted to carry out repairs. Critical Components: These products are not authorised for use as critical components in nuclear control systems, life support systems or equipment for use in hazardous environments without the express written approval of the Managing Director of TDK- Lambda EMEA.
  • Page 2 Internal fuses protect the unit and must not be replaced by the user. In case of internal defect, the unit must be returned to TDK-Lambda UK LTD or one of their authorised agents. A suitable mechanical, electrical and fire enclosure must be provided by the end use equipment for mechanical, electric shock and fire hazard protection.
  • Page 3 Allgemeine Sicherheitsvorschriften: LESEN SIE DIE SICHERHEITSVORSCHRIFTEN Wartung: Diese Produkte können nicht durch den Kunden gewartet werden. Nur TDK-Lambda UK LTD. und deren zugelassene Vertriebshändler sind zur Durchführung von Reparaturen berechtigt. Kritische Komponenten: Diese Produkte sind nicht für die Verwendung als kritische Komponenten in nuklearen Kontrollsystemen, Lebenserhaltungssystemen oder Geräten in gefährlichen Umgebungen geeignet, sofern dies nicht ausdrücklich und...
  • Page 4 Für ummantelt Produkte, verwenden Sie keine Schrauben, die das Gerät mehr als durchdringen; siehe Zeichnung Eine interne Sicherung schützt das Gerät und darf durch den Benutzer nicht ausgetauscht werden. Im Fall von internen Defekten muss das Gerät an TDK-Lambda UK LTD oder einen der autorisierten Vertriebshändler zurückgeschickt werden.
  • Page 5 Consignes générales de sécurité: LIRE LES CONSIGNES DE SECURITE Entretien: Ces produits ne peuvent pas être réparés par l’utilisateur. Seuls, TDK-Lambda UK LTD et ses agents agréés sont autorisés à effectuer des réparations. Composants critiques: Ces produits ne doivent pas être utilisés en tant que composants critiques dans des systèmes de commande nucléaire, dans des systèmes de sauvetage ou dans des équipements utilisés dans des environnements dangereux,...
  • Page 6 Un fusible interne protège le module et ne doit pas être remplacé par l'utilisateur. En cas de défaut interne, le module doit être renvoyé à TDK-Lambda UK LTD ou l'un de ses agents agréés. Une enceinte appropriée doit être prévue par l'utilisateur final pour assurer la protection contre les chocs mécaniques, les chocs électriques et l'incendie.
  • Page 7 Manutenzione: Il cliente non può eseguire alcuna manutenzione su questi prodotti. L'esecuzione delle eventuali riparazioni è consentita solo a TDK-Lambda UK LTD e ai suoi agenti autorizzati. Componenti critici: Non si autorizza l'uso di questi prodotti come componenti critici all'interno di sistemi di controllo nucleari, sistemi necessari alla sopravvivenza o apparecchiature destinate all'impiego in ambienti pericolosi, senza l'esplicita approvazione scritta dell'Amministratore Delegato di TDK-Lambda EMEA.
  • Page 8 Un fusibile interno protegge l'unità e non deve essere sostituito dall'utente. Nell'eventualità di un difetto interno, restituire l'unità a TDK-Lambda UK LTD o a uno dei suoi agenti autorizzati. L'apparecchiatura finale deve includere una recinzione meccanica, elettrica e antincendio per proteggere dai pericoli di natura meccanica, dalle scosse elettriche e dai pericoli di incendio.
  • Page 9 Instrucciones generales de seguridad: LEA LAS INSTRUCCIONES DE SEGURIDAD Servicio: Estos productos no pueden ser reparados por los clientes. TDK-Lambda UK LTD. y sus agentes autorizados son los únicos que pueden llevar a cabo las reparaciones. Componentes fundamentales: Estos productos no pueden ser utilizados como componentes fundamentales en sistemas de control nuclear, sistemas de soporte vital o equipos a utilizar en entornos peligrosos sin el consentimiento expreso por escrito del Director General de TDK-Lambda EMEA.
  • Page 10 Un fusible interno protege la unidad y este no debe ser nunca reemplazado por el usuario. En caso de existir algún defecto interno, la unidad debe ser enviada a TDK-Lambda UK LTD o a uno de sus agentes autorizados. El equipo de uso final debe constituir un recinto de protección mecánica, eléctrica y contra incendios de protección mecánica, contra descargas eléctricas y contra el peligro de incendios.
  • Page 11 Instruções gerais de segurança: LEIA AS INSTRUÇÕES DE SEGURANÇA Manutenção: Estes produtos não são podem ser submetidos a manutenção por parte do cliente. Apenas a TDK-Lambda UK LTD e os seus agentes autorizados têm permissão para realizar reparações. Componentes essenciais: Não é...
  • Page 12 Existe um fusível interno que protege a unidade e que não deve ser substituído pelo utilizador. Em caso de defeito interno, a unidade deve ser devolvida à TDK-Lambda UK LTD ou a um dos seus agentes autorizados. O equipamento de utilização final deve fornecer um bastidor com protecção mecânica, eléctrica e contra incêndios adequada.
  • Page 13 TDK-Lambda ZWD150PAF Series INSTRUCTION MANUAL ZWD150PAF Series Instruction Manual BEFORE USING THE POWER SUPPLY UNIT Pay attention to all warnings and cautions before using the unit. Incorrect usage could lead to an elec- trical shock, damage to the unit or a fire hazard.
  • Page 14 TDK-Lambda ZWD150PAF Series INSTRUCTION MANUAL 1. Terminal Explanation 1-1. ZWD150PAF  L: AC Input terminal (pin 6 of CN1) -R : CN3 ON/OFF control -R terminal Live line (fuse in line) +R : CN3 ON/OFF control +R terminal  N: AC input terminal (pin 4 of CN1) Neutral line *Input &...
  • Page 15 TDK-Lambda ZWD150PAF Series INSTRUCTION MANUAL 1-2. ZWD150PAF/J  L: AC Input terminal (pin 1 of CN1) Live line (fuse in line)  -R : CN3 ON/OFF control -R terminal N: AC input terminal (pin 3 of CN1) Neutral line +R : CN3 ON/OFF control +R terminal ...
  • Page 16 TDK-Lambda ZWD150PAF Series INSTRUCTION MANUAL 1-3. ZWD150PAF/T -R : CN3 ON/OFF control -R terminal  L: AC Input terminal L (M4 screw) +R : CN3 ON/OFF control +R terminal Live line (fuse in line)  N: AC input terminal N (M4 screw) Neutral line * Input &...
  • Page 17 TDK-Lambda ZWD150PAF Series INSTRUCTION MANUAL 2. Terminal Connecting Method Pay attention to the input wiring. If it is connected to the wrong terminal, the power supply will be damaged. · Input must be turned off when making connections. · Connect FG terminal of input connector and mountable PE to ground terminal of the equipment.
  • Page 18 TDK-Lambda ZWD150PAF Series INSTRUCTION MANUAL ZWD150PAF/J ZWD150PAF/T - 5 -...
  • Page 19 TDK-Lambda ZWD150PAF Series INSTRUCTION MANUAL Explanation of Function and Precautions 3-7. Output Ripple & Noise 3-1. Input Voltage Range The standard specification for maximum ripple and noise value Input voltage range is single phase 85 ~ 265VAC ( 47 ~ 63Hz ) is measured according to measurement circuit specified below.
  • Page 20 4) Formula: For ZWD150PAF series, the peak output current should satisfy the conditions below: ZWD150PAF: Io(ave) = Ip x D + Im x (1-D) ≤ Io spec. 1)Should not exceed the rated peak current in the specification. (refer to derating curve) (eg.
  • Page 21 TDK-Lambda ZWD150PAF Series INSTRUCTION MANUAL 3-13. Withstand Voltage 3-14. External connection of circuit with protective seperation This series is designed to withstand 3.0kVAC between input and output, 2.0kVAC between input and PE (Chassis) and All the outputs is protected using protection of SELV. ( As per 500VAC between output and the PE (Chassis) each for 1 mi- required in the EN50178, clause 5.2.8)
  • Page 22 TDK-Lambda ZWD150PAF Series INSTRUCTION MANUAL 4. Mounting Directions With chassis and with chassis&cover type mounting 4-1. Output Derating according to the Mounting Direc- method tions Recommended standard mounting method is (A). Method (B), (C), (D), (E) are also possible. Mounting (F), (G), (H), (I) are...
  • Page 23 TDK-Lambda ZWD150PAF Series INSTRUCTION MANUAL · Output Derating Forced air cooling PCB type and with chassis type · Convection cooling PCB type and with chassis type 1 0 0 Mounting (A),(B),(C),(D),(E) Mounting (A),(B) Mounting (C),(D),(E) Ta (°C) Forced air Average Load (%) -1 0 T a (°...
  • Page 24 TDK-Lambda ZWD150PAF Series INSTRUCTION MANUAL 4-2. Mounting Method Hatching area is maximum permissible area of metal part for mounting. PCB type Please use the mounting holes (5 holes of f3.5) and insert the spacer (MAXf8.0)of height over 8mm to lift the unit. Also use all 5 mounting holes for the unit installation.
  • Page 25 TDK-Lambda ZWD150PAF Series INSTRUCTION MANUAL ( K ) ( J ) ( L ) Output Input 7. Before concluding that the unit is at fault... Input Before concluding that the unit is at fault, make the following checks. · Check if the rated input voltage is connected.