Fan characteristics
Install volume dumpers to the air discharge ducts. Adjust the air volume within the range of 80 to approximately
120 % of the standard air volume.
AP0304H2UL, AP0364H2UL
Power source: 208 V / 60 Hz
External static pressure
Standard air flow rate
tap
(in.WG)
(cfm)
High
1.075
Middle
0.641
926
Low
0.287
2.50
High tap
2.00
Middle tap
Low tap
1.50
1.00
700
750
800
850
900
950
1000 1050 1100 1150 1200
Air flow rate (cfm)
1.400
1.200
High tap
1.000
0.800
Middle tap
0.600
0.400
Low tap
0.200
0.000
700
750
800
850
900
950
1000 1050 1100 1150 1200
Air flow rate (cfm)
11-EN
Power source: 230 V / 60 Hz
External static pressure
Standard air flow rate
tap
(in.WG)
(cfm)
High
1.175
Middle
0.814
926
Low
0.506
2.50
High tap
2.00
Middle tap
Low tap
1.50
1.00
700
750
800
850
900
950
1000 1050 1100 1150 1200
Air flow rate (cfm)
1.400
1.200
High tap
1.000
Middle tap
0.800
0.600
Low tap
0.400
0.200
0.000
700
750
800
850
900
950
1000 1050 1100 1150 1200
Air flow rate (cfm)
AP0484H2UL
Power source: 208 V / 60 Hz
External static pressure
Standard air flow rate
tap
(in.WG)
(cfm)
High
0.606
Middle
0.296
1235
Low
–
2.50
2.00
Middle tap
1.50
1.00
950
1000 1050
1100 1150 1200 1250 1300 1350 1400 1450 1500
Air flow rate (cfm)
1.200
1.000
0.800
High tap
0.600
Middle tap
0.400
0.200
0.000
950
1000 1050
1100 1150 1200 1250 1300 1350 1400 1450
Air flow rate (cfm)
– 6 –
Power source: 230 V / 60 Hz
External static pressure
Standard air flow rate
tap
(in.WG)
High
0.801
Middle
0.519
Low
0.114
2.50
High tap
High tap
2.00
Middle tap
Low tap
1.50
1.00
950
1000 1050
1100 1150 1200 1250 1300 1350 1400 1450 1500
Air flow rate (cfm)
1.200
1.000
High tap
0.800
Middle tap
0.600
0.400
Low tap
0.200
0.000
1500
950
1000 1050
1100 1150 1200 1250 1300 1350 1400 1450
Air flow rate (cfm)
(cfm)
1235
1500
EN
12-EN