When the input frequency is within 46 to 64Hz, the UPS can
be set to a constant output frequency, 50 Hz or 60 Hz. The
UPS will still charge the battery in this mode.
When the input voltage is beyond the acceptable range or if
there is a power failure, the UPS will back up the power from
the battery and the alarm will beep every 4 seconds.
When the input voltage is within the acceptable range and the
bypass is enabled, turn off the UPS and it will enter in Bypass
mode. The alarm beeps every two minutes.
When the UPS is in AC mode or CVCF mode, press the "Test"
key for more than 0.5s. Then the UPS will beep once and start
a "Battery Test". The line between I/P and the inverter icons
will flash to remind users. This operation is used to check the
battery status.
When a fault occurs, the UPS will display fault messages on
the LCD panel.