Installation servicing space

The numerical figures used in the figures represent the dimensions in
mm.
(Refer to "Precautions on installation" on page 5)
Precaution
(A) In case of non-stacked installation figure 1A and figure 1B
Suction side obstacle
Discharge side obstacle
Left side obstacle
Right side obstacle
Top side obstacle
NOTE
Minimum distance B1 in figure 1A and figure 1B
mentions the space required for correct operation
of the unit. Required space for servicing though is
12 inch (300 mm).
(B) In case of stacked installation
1.
In case obstacles exist in front of the outlet side.
A
≥40 inch (≥1000 mm)
2.
In case obstacles exist in front of the air inlet.
A
≥12 inch (≥300 mm)
Do not stack more than one unit.
About 4 inch (100 mm) is required as the dimension for laying the
upper unit's drain pipe. Get the portion A sealed so that air from the
outlet does not bypass.
Installation manual
6
Obstacle is present
1
In these cases, close the
bottom of the installation
frame to prevent the
discharged air from
being bypassed
2
In these cases, only
2 units can be installed.
This situation is not
allowed
(C) In case of multiple-row installation (for roof top use, etc.)
1.
In case of installing one unit per row.
≥8 inch (≥200 mm)
≥40 inch (≥1000 mm)
2.
In case of installing multiple units (2 units or more) in lateral
connection per row.
H
≥60 inch (≥1500 mm)
Relation of dimensions of H, A and L are shown in the table below.
L
0<L≤1/2H
L≤H
1/2H<L
H<L
Installation not allowed
EDLQ036~054BA6VJU1 + EBLQ036~054BA6VJU1
≥4 inch (≥100 mm)
≥80 inch (≥2000 mm)
L
A
≥120 inch (≥3000 mm)
≥24 inch (≥600 mm)
A
10 (250)
12 (300)
Unit for air to water heat pump system
4PW56182-1