I.3.7
Probes Menu
The pr obes menu allows to display the analogue digital inputs and
outputs. It also allows to displ ay information regarding the state of the
mac hine ad the software i nstalled.
To access the Probes menu, proceed as described:
Press the Prg key for 3 s econds.
!
ALARM
>
Setpoints menu
Probe menu
Prg
Condensing control
Rem. Summer/Winter
ON
OFF
Using the DOW N key scroll the lines until reaching Prob es m enu.
!
ALARM
Setpoints menu
>
Probe menu
Prg
Condensing control
Rem. Summer/Winter
ON
OFF
Press the MODE/Enter key to access the sub-menus.
!
ALARM
Analog inputs:
Prg
B1:
B2:
ON
OFF
Use the UP/DOW N keys to access the following mas ks:
Analogue inputs:
B1:
00.0°C
B2:
00.0°C
The meaning to be attributed to eac h anal ogue input can var y
depending on the application and the type of machine.
B1
Evaporator i nput water temperature (ST1)
B2
Analogue input Set-point (4-20mA) (¹)
Outdoor air temper ature (²)
DHW temperature (³)
NOTES
(1) – If Set-point function enabled from analogue input.
(2) – If outdoor air temperature probe pres ent.
(3) – If DHW function enabled (for the following models: TCAEY
105÷111, THAEY 105÷111 NF, TCAEY-THAEY 115÷265, TCAEY-
THAEY 118÷136 H.E., TCHEY–THHEY 105÷112).
MODE
MODE
MODE
00.0 C
00.0 C
Analogue inputs
B3
External heat exchange temperature (¹)
Condenser outl et water temperature (²)
NOTES
(1) – Enabl ed if pressur e probe not enabled (onl y for THAEY 105÷111
NF, THAEY 115÷233).
(2) – Onl y for TCHEY–THHEY 105÷112 TCHEY–THHEY 115÷4450.
B4
Storage tank output water temperature (¹)
Condenser i nput water temperature (²)
NOTES
(1) – Pres ent on unit with storage tank ( onl y for TCAEY-THAEY
115÷265, TCAEY-THAEY 118÷136 H.E. e TCAEY-THAEY 270÷4320).
(2) – Onl y for TCHEY–THHEY 105÷112 e TCHEY–THHEY 115÷4450
with H PH access or y.
B5
Evaporator output water temperature
B6
Condenser pressure (¹)
NOTES
(1) – Onl y for TCHEY–THHEY 115÷2185.
B7
DHW temperature
B8
Recover y outlet water temperature
B9
Circuit 2 condenser pressure
Digital inputs
M: CCCCCCOO
Digital outputs
M: 00000000
Analogue outputs
Y0:
- - - %
Supply
Voltage L1
000V
Voltage L2
000V
Voltage L3
000V
Code: FLRHSmCHIO_AI
+CA 64 ar eas
Ver.: A00 00/00/00
Bios:
.00 00/00/00
Boot:
.00 00/00/00
Manual: [manual code]
Ver.>=
0.00 00/00/00
In the c ase of "Adapti veFunction Pl us" function enabl ed, the followi ng
mas ks are displayed:
Temperature:
10.8°C
SET point:
07.0°C
HI Threshold:
09.0°C
LO Threshold:
05.0°C
Averag e_Temp:
07.2°C
FC_tot/comp:
28/28
Press the Prg key for 3 s econds to go bac k to the previ ous menu.
53
CONTROL PANELL PGD
Digital inputs
State of the inputs
Digital outputs
State of the inputs
Analogue outputs
Fan speed reg. signal.
Power suppl y
Voltage L1
Voltage L2
Voltage L3
Softwar e code
Softwar e version
Bios Version
Boot version
Current control temperature
Current Set-poi nt
Compress ors s witch-on/off threshold
Average temperature of an ON/OFF
cycle
Estimate of the load fracti on